EVCO S.p.A.
EV3 HP & EVD HP | Installer manual ver. 1.2 | Code 1443DHPE124
page 29 of 52
M
CF17
0
0
2
- - - -
IN1 output configuration type
0= Temperature [°C]
1= 4-20mA [Bar]
2= Not used
The choice of CF17 value determines the unit of
measurement for the condensation (°C or Bar)
M
CF31
0,0
-50,0
80,0
Bar
Start of condensation pressure scale
M
CF32
50,0
-50,0
80,0
Bar
Bottom of condensation pressure scale
M
CF35
2
0
4
- - - -
AO1 output configuration type
0= Disabled
1= Phase cutting [%]
2= 0-10V [%]
3= PWM [%]
4= Frequency [Hz]
The choice of CF35 value determines the unit of
measurement for adjusting the compressor (Hz or %)
M
CF36
1
0
4
- - - -
AO2 output configuration type
0 = Disabled
1= Phase cutting [%]
2= 0-10V [%]
3= PWM [%]
4= Frequency [Hz]
The choice of CF36 value determines the unit of
measurement for adjusting the fan (Hz or %)
M
CF47
0
0
4
- - - -
AO1 analogue output function configuration
0= Disabled
1= Not used
2= Not used
3= Not used
4= Modulating compressor
S
CF51
0
0
1
- - - -
RUN Logo
0= Off
1= On
MENU
PARAM.
DEFAULT
MIN.
MAX.
U.M.
ALARMS
M
AL01
3
0
255
- - - -
Number of alarms in an hour for low pressure after which
the alarm switches from automatic to manual re-arm
M AL02
120
0
255
s
Low pressure alarm bypass time
M
AL03
-20,0
-50.0
80.0
°C-Bar
Low pressure alarm set-point