C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
47
PF64
Fan inverter
minimum
Circuit 3
Differential for fan
regulation with circuit 3
inverter
0.5
0.0
20.0
Bar
IS-RF
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
PF65
Fan inverter SP
offset.
Circuit 3
Suction setpoint offset for
circuit 3 inverter regulation
of the fan.
0.0
-20.0
20.0
Bar
IS-RF
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
PF66
Fan inverter
minimum
Circuit 3
Minimum fan value with
circuit 3 inverter
0.0
0.0
100.0
%
IS-RF
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
PF67
Fan inverter
speedup
Circuit 3
Fan speedup time with
circuit 3 inverter
2
0
999
Sec
IS-RF
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
PF68
Fan inverter time
Circuit 3
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 3
neutral zone reg.)
10
0
999
Sec
IS-RF
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
PF01
Fan rotation
Type of rotation used for
fan management:
0: FIFO
1: LIFO
2: FIFO + time
3: LIFO + time
FIFO
FIFO (0)
LIFO
+ time
(3)
IS-F
PF02
Enable
compressor
regulation
If enabled, allows selection
of fan regulation, only if at
least one compressor is on
NO
NO (0)
YES (1)
IS-F
PF07
TOnOther
Minimum time that must
elapse before another fan
can be switched on
2
0
999
Sec
IS-F
PF08
TOffOther
Minimum time that must
elapse before another fan
can be switched off
2
0
999
Sec
IS-F
PF11
Fan probe error
Circuit 1
Number of fans that will be
forced if an alarm occurs on
the circuit 1 supply probe
1
0
PG41
IS-F
PF31
Fan probe error
Circuit 2
Number of fans that will be
forced if an alarm occurs on
the circuit 2 supply probe
1
0
PG45
IS-F
Visible if PG01
> 1 and
PG30 = 0
PF51
Fan probe error
Circuit 3
Number of fans that will be
forced if an alarm occurs on
the circuit 3 supply probe
1
0
PG51
IS-F
Visible if PG01
> 2 and
PG30 = 0
PF71
Enable floating
condensation
Enables floating
condensation for fan
management
NO
NO (0)
YES (1)
IS-F
Содержание C-PRO GIGA
Страница 6: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 6 C PRO MEGA ...
Страница 7: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 7 C PRO GIGA ...
Страница 14: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 14 2 5 2 C PRO GIGA RACK electrical connections ...
Страница 22: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 22 2 7 2 C PRO EXP GIGA electrical connections ...
Страница 26: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 26 3 COMPONENT NETWORK AND ACCESSORIES 3 1 Example ...
Страница 50: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 50 compensation line neutral zone 0 NO 1 YES ...