C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
38
PM21..30
Compressor
forcing
(1..10)
In manual operation, this
sets the number of forced
compressor steps
0
0
4
MA-M
Compressors 1
to 10; Visibility
*¹
PM33
PM34
Enable
compressor
(11-12)
Enables manual/automatic
operation of each
compressor:
M: manual
A: normal operation
A
A (0)
M (1)
MA-M
Compressors
11 and 12;
Visibility
*¹
PM35
PM36
Compressor
forcing
(11-12)
In manual operation, this
sets the number of forced
compressor steps
0
0
4
MA-M
Compressors
11 and 12;
Visibility
*¹
PM37
Comp. inverter
forcing Circuit 1
In manual operation, this
forces the compressor with
the circuit 1 inverter
0
0
100.0
%
MA-M
PM38
Comp. inverter
forcing Circuit 2
In manual operation, this
forces the compressor with
the circuit 2 inverter
0
0
100.0
%
MA-M
PM39
Comp. inverter
forcing Circuit 3
In manual operation, this
forces the compressor with
the circuit 3 inverter
0
0
100.0
%
MA-M
PM51..60
Enable
fan
(1..10)
Enables manual/automatic
operation of each fan:
M: manual
A: normal operation
A
A (0)
M (1)
MA-M
Fans 1 to 10;
Visibility
*²
PM61..70
Fan forcing
(1..10)
In manual operation, this
forces the fans to be
switched on and off:
S: fan off
A: fan on
S
S (0)
A (1)
MA-M
Fans 1 to 10;
Visibility
*²
PM73
PM74
Enable
fan
(11-12)
Enables manual/automatic
operation of each fan:
M: manual
A: normal operation
A
A (0)
M (1)
MA-M
Fans 11 and 12;
Visibility
*²
PM75
PM76
Fan forcing
(11-12)
In manual operation, this
forces the fans to be
switched on and off:
S: fan off
A: fan on
S
S (0)
A (1)
MA-M
Fans 11 and 12;
Visibility
*²
PM77
Circuit 1 inverter
fan forcing
In manual operation, this
forces the fan with the
circuit 1 inverter
0
0
100.0
%
MA-M
PM78
Circuit 2 inverter
fan forcing
In manual operation, this
forces the fan with the
circuit 2 inverter
0
0
100.0
%
MA-M
PM79
Circuit 3 inverter
fan forcing
In manual operation, this
forces the fan with the
circuit 3 inverter
0
0
100.0
%
MA-M
PM81
Suction probe 1
calibration
Circuit 1 suction probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
PM82
Suction probe 2
calibration
Circuit 2 suction probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
Visible if PG01
> 1
Содержание C-PRO GIGA
Страница 6: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 6 C PRO MEGA ...
Страница 7: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 7 C PRO GIGA ...
Страница 14: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 14 2 5 2 C PRO GIGA RACK electrical connections ...
Страница 22: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 22 2 7 2 C PRO EXP GIGA electrical connections ...
Страница 26: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 26 3 COMPONENT NETWORK AND ACCESSORIES 3 1 Example ...
Страница 50: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 50 compensation line neutral zone 0 NO 1 YES ...