C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
39
PM83
Suction probe 3
calibration
Circuit 3 suction probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
Visible if PG01
> 2
PM84
Supply probe 1
calibration
Circuit 1 supply probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
PM85
Supply probe 2
calibration
Circuit 2 supply probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
Visible if PG01
> 1 and PG30 =
0
PM86
Supply probe 3
calibration
Circuit 3 supply probe
calibration
0.0
-9.9
9.9
Bar
MA-IO
Visible if PG01
> 2 and PG30 =
0
PM87
Environment
temperature
probe calibration
Calibration of the
environment temperature
probe
0.0
-9.9
9.9
Bar
MA-IO
PM88
External
temperature
probe calibration
Calibration of the external
temperature probe
0.0
-9.9
9.9
Bar
MA-IO
INSTALLER MENU PARAMETERS
PC12
Compressor min.
setpoint
Circuit 1
Minimum suction setpoint
value pertaining to the
compressors of circuit 1
0.1
PH01
SPC1
Bar
IS-RC
PC13
Compressor
max. setpoint
Circuit 1
Maximum suction setpoint
value pertaining to the
compressors of circuit 1
2.5
SPC1
PH02
Bar
IS-RC
PC14
Compressor
regulation
Circuit 1
Sets the type of regulation
for controlling the circuit 1
compressors
Neutral
Zone (1)
Side
Band (0)
Neutral
Zone (1)
IS-RC
PC16
Compressor
integral time
Circuit 1
Integral time Ti for side
band regulation of circuit 1
compressors
600
0
999
Sec
IS-RC
Visible if PC14
= 0
PC17
Compressor
proportional
band. Circuit 1
Proportional band Bp for
side band regulation of
circuit 1 compressors
0.5
0
20.0
Bar
IS-RC
Visible if PC14
= 0
PC18
Comp. zone
Circuit 1
Zone value for neutral zone
regulation of circuit 1
compressors
0.5
0
20.0
Bar
IS-RC
Visible if PC14
= 1
PC19
Comp. zone
differential
Circuit 1
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 1
0.5
0
20.0
Bar
IS-RC
Visible if PC14
= 1
PC20
Compressor
TOnMin
Circuit 1
Minimum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)
20
0
PC21
Sec
IS-RC
Visible if PC14
= 1
PC21
Compressor
TOnMax
Circuit 1
Maximum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)
60
PC20
999
Sec
IS-RC
Visible if PC14
= 1
PC22
Compressor
TOffMin
Circuit 1
Minimum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)
10
0
PC23
Sec
IS-RC
Visible if PC14
= 1
PC23
Compressor
TOffMax
Circuit 1
Maximum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)
60
PC22
999
Sec
IS-RC
Visible if PC14
= 1
PC24
Comp. inverter
diff.
Circuit 1
Differential for compressor
regulation with circuit 1
inverter
0.5
0.0
20.0
Bar
IS-RC
Visible if PG12
= 1
PC25
Compressor
inverter SP
Suction setpoint offset for
circuit 1 inverter regulation
0.0
-20.0
20.0
Bar
IS-RC
Visible if PG12
= 1
Содержание C-PRO GIGA
Страница 6: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 6 C PRO MEGA ...
Страница 7: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 7 C PRO GIGA ...
Страница 14: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 14 2 5 2 C PRO GIGA RACK electrical connections ...
Страница 22: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 22 2 7 2 C PRO EXP GIGA electrical connections ...
Страница 26: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 26 3 COMPONENT NETWORK AND ACCESSORIES 3 1 Example ...
Страница 50: ...C PRO MEGA RACK C PRO GIGA RACK APPLICATION MANUAL Page 50 compensation line neutral zone 0 NO 1 YES ...