EVCO S.p.A.
c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104
page 58 of 62
Digital inputs:
According to the model:
•
5 optoisolated inputs at 24 VAC / DC of which 2 up to 2 KHz and 3 at 50 / 60 Hz in
c-pro 3 micro, c-pro 3 kilo, c-pro 3 EXP micro and c-pro 3 EXP kilo
•
9 optoisolated inputs at 24 VAC / DC of which 2 up to 2 KHz and 7 at 50 / 60 Hz in
c-pro 3 micro+, c-pro 3 kilo+, c-pro 3 EXP micro+ and c-pro 3 EXP kilo+
Optoisolated digital inputs at 24 VAC / DC
Power supply:
24 VAC (±15%), 50 / 60 Hz (±3 Hz) or 24 VDC (+66% -16%).
Input resistance:
≥
to 10K
Ω
.
Protection:
no protection.
Displays:
c-pro 3 micro and c-pro 3
micro+
c-pro 3 kilo and c-pro 3
kilo+
I/O expansions
According to the model:
•
4 + 4 digits custom
display
(with
function icons)
•
nothing
(blind
version).
According to the model:
•
128 x 64 pixel
single colour LCD
graphic
display
(black
with
rearlighting
through
white
LEDs)
•
4 + 4 digits custom
display
(with
function icons)
•
nothing
(blind
version).
Nothing (blind version).
Analog outputs:
3 non optoisolated outputs in c-pro 3 micro, c-pro 3 kilo, c-pro 3 EXP micro and c-pro 3
EXP kilo:
•
2 outputs configurable via configuration parameter for PWM / 0-10 V signal
•
1 output configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V
signal.
6 non optoisolated outputs in c-pro 3 micro+, c-pro 3 kilo+, c-pro 3 EXP micro+ and c-pro 3
EXP kilo+:
•
2 outputs configurable via configuration parameter for PWM / 0-10 V signal
•
2 outputs configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V
signal
•
2 outputs for 0-10 V signal.
PWM analog outputs
Driving power supply:
10 VDC (+16% -25%), 10 mA max.
Frequency:
0... 2 KHz.
Duty:
0... 100%.
Protection:
no protection.