EVCO S.p.A.
c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104
page 41 of 62
Networks /
UART1 (1)
Baud Rate
- - -
- - -
- - -
9600
Modbus communication baud rate in a
RS-485 network wired on the RS-485 port
with Modbus slave communication protocol
1200
= 1,200 baud
2400
= 2,400 baud
4800
= 4,800 baud
9600
= 9,600 baud
19200
= 19,200 baud
28800
= 28,000 baud
38400
= 38,400 baud
57600
= 57,600 baud
Networks /
UART1 (1)
Parity
- - -
- - -
- - -
EVEN
Modbus communication parity in a RS-485
network wired on the RS-485 port with
Modbus slave communication protocol
NONE
= no parity
ODD
= odd
EVEN
= even
Networks /
UART1 (1)
Stop
- - -
- - -
- - -
1 BIT
Modbus communication stop bit number in a
RS-485 network wired on the RS-485 port
with Modbus slave communication protocol
1 BIT
= 1 bit
2 BIT
= 2 bit
Networks /
UART1 (1)
Timeout
2
240
s
10
Modbus communication time-out in a
RS-485 network wired on the RS-485 port
with Modbus slave communication protocol
for the test of the remote values of the I / O
(after
this
time
without
Modbus
communication, the request is considered
not sent and the controller moves to the
following request) (1)
Networks /
UART1 (1)
Address
1
247
- - -
1
local (or of the controller) Modbus node
address in a RS-485 network wired on the
RS-485
port
with
Modbus
slave
communication protocol