To modify the real date and time operate as follows:
19.
From step 2, press and release button UP or button DOWN to select the voice Data e ora reale.
20.
Press and release button ENTER.
21.
Press and release button UP or button DOWN to modify the value.
22.
Press and release button ENTER or button RIGHT to confirm the value and modify the following field (press and release
button LEFT or button RIGHT to move among the fields).
23.
Repeat steps 21 and 22.
To copy the parameters from the controller to an USB peripheral operate as follows:
24.
Make sure the power supply is switched on.
25.
Connect the peripheral to the controller.
26.
Gain access to the submenu Backup / Restore, then choose Parameter key (choose Backup memory for the backup
memory).
27.
Press and release button UP or button DOWN to select “Application par” to copy the application software parameters or
“Hardware config” to copy the configuration parameters.
28.
Press and release button UP or button DOWN to select “Save on the key”.
29.
Press and release button ENTER: the parameters will be copied from the controller to the peripheral (this operation usually
takes a few seconds; if an error had to arise the LED system alarm (look at paragraph 5.2.1 “LEDs at the fron of the device”)
will light up and parameter Key Par (it belongs to the Diagnostic submenu) will assume value Err.
30.
Disconnect the programming key.
To copy the parameters from an USB peripheral to the controller operate as follows:
31.
Make sure the power supply is switched on.
32.
Connect the peripheral to the controller.
33.
Gain access to the submenu Backup / Restore, then choose Parameter key (choose Backup memory for the backup
memory).
34.
Press and release button UP or button DOWN to select “Restore from the key”.
35.
Press and release button ENTER: the parameters will be copied from the peripheral to the controller (this operation usually
takes a few seconds; if an error had to arise the LED system alarm (look at paragraph 5.2.1 “LEDs at the fron of the device”)
will light up and parameter Key Par (it belongs to the Diagnostic submenu) will assume value Err.
36.
Disconnect the peripheral.
The copy of the parameters from the programming key EVKEY10 to the controller is allowed on condition that the
firmware of the controllers coincides.
To quit the procedure operate as follows:
37.
Press and release button ESC over and over again: possible modifications will not be saved.
Switch off the power supply after the modification of the configuration.