8
3.6 Blowdown Valve and Timer Connections
The Pulse~Pure Integrated Controller allows 5 Amps of current for incoming power of
120V, 230V or 460V for operating a conductivity-actuated blowdown valve and timer-
actuated device.
Make all connections to the DIN rail located inside the Pulse~Pure Panel at the bottom.
Feed wires from the devices through waterproof stress-relief cord grips provided.
Connect the HOT lead from blowdown valve to the
BLDN
terminal and NEUTRAL to
#2
terminal. Connect the HOT lead from a timer-actuated device, to the
TMR
terminal and
NEUTRAL wire to
#2
terminal. See
Figure 6.
Figure 6 DIN Rail Connections for Blowdown
Valve and Timer-Actuated Device
Connect
HOT
lead from Timer-
Actuated Device to
TMR
terminal.
Connect
HOT
lead from Blowdown
Valve to
BLDN
terminal.
Connect
NEUTRAL
leads
from Blowdown Valve and
Timer-Actuated Device to
#2
terminals.