7.2
Procedure for Evaluation of Conductivity Sensor
Try cleaning the sensor first (refer to Section 6.1). Check the sensor connections to the terminal strip.
Make sure that the correct colors go to the correct terminals the connections are tight and that the
connectors are pinching on exposed wire lead, not insulation. Restore power and check to see if the
conductivity is back to normal. If not, replace sensor.