14
Local Password
Enable Security. Select Local Password from Menu. The user can enter their own Local Password (up to
10 digits). Accept the new Password by touching the Confirm icon.
Record the new passcode and keep it
in a safe place. The Factory cannot reset forgotten or lost Local Passwords.
5.2.3 Display Settings
Note: Changing “Home” Screen display assignments may affect operation. Do not attempt to
modify the settings without prior approval from Evapco Water Systems.
Adjust Display
From the Main Menu screen, select Configuration Settings. Select Display Settings. Touch the Scroll
Down icon until Adjust Display is observed and select it. Adjust Brightness and contrast slide bar to
achieve desired appearance. When complete select the Confirm icon to accept the change.
Key Beep
Key Beep factory default setting is disabled. To enable, select Configuration on the Main Menu. Select
Display Settings. Touch the Scroll Down Button until Key Beep is displayed and select. Select Enabled
and press the Confirm icon to accept the change.
5.2.4 File Utilities
The controller collects and stores data for user download to a standard USB flash drive. The controller has
three logs, Datalog, Event Log, and Reset Log. All files are in a CSV format that may be opened in a
spreadsheet such as Microsoft Excel.
Datalog
Contains the following data taken at 1-hour intervals for the past two months:
Conductivity
Conductivity Set Point Temperature
Water Meter 1 and 2 Totals (if equipped)
After two months, the oldest data will be overwritten with new data. The file will always
contain the last two months of data.
Event Log
Records set point changes, user calibrations, alarms, relay status changes (noted by change from 0
to 1 in log), file exports, etc.
System Log
This records hardware changes, automatic calibrations, power loss, etc..
Data Log Range
The controller default setting is 2 months. To change, select Configuration from the Main Menu screen.
Select File Utilities. Select Data Log Range. Ranges from
“
Since Previous
”
to 3 Months are available for
the User to select. Touch the desired range and select the Confirm icon to accept.
Log Frequency
The controller default setting is 1 hour. To change, select Configuration from the Main Menu screen.
Select File Utilities. Select Log Frequency. The controller data log frequency selections range from 15
minutes to 1 Day.