Identification
7100A User Manual
1-7
1.2. TECHNICAL SPECIFICATIONS
Use
In accordance with product standard EN 60947-4-3:
Devices for continuous duty:
Thyristor unit variant 4:
4-20 mA analogue input signal (ATP input)
or digital communication option.
Configuration as product code.
1.2.1. Power
Nominal current
16A to 250A at 45°C (see product code)
Nominal voltage
100 V to 500 V (see code).
Main Frequency
50 Hz +/- 3 Hz and 60 +/- 3 Hz
Dissipated power
1.3 W (approx.) per amp.
Cooling
Ratings up to 200 A: Natural convection
@ 250 A: 115 V or 230 V fan,
consumption 10 VA
1.2.2. Load
Single-phase industrial load:
Categories of use
The categories of use applicable for each unit are indicated on
the identification label
• AC-51 Non-inductive or low inductance loads,
furnace resistances
(Resistive load with low temperature coefficient).
• AC-55b Switching of incandescent lamps
(Short wave infrared elements, SWIR units
≤
100 A only).
• AC-56a Switching of transformers
(Transformer primaries and
high temperature coefficient resistive loads).
1.2.3. Dimensions
Rating (A) Height (mm)
Length (mm)
Depth (mm)
All
Lite
Full
Lite
Full
Options
Base (1)
Option (2)
16 to 40 164
52,5
70
193
218
237
63
164
70
70
212
237
237
80 to 100
226
96
96
215
243
243
125 to 250
423
144
N/A
372
372
N/A
Note (1) : Basic product, without alarm option or control (except V2 and OL)
Note (2) : Product with
one control option (I2 or V2CL) or
one alarm option (GRF or DLF)