![Eurotherm 451 Series Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/eurotherm/451-series/451-series_user-manual_2440573051.webp)
455-461 Series
Automatic
input signal
DIL-switch position
1
2
3
4
0-5 V
0
0
0
0
0-10 V
1
0
0
0
1-5 V
0
1
0
0
0-5 mA
0
0
I
0
0-10 mA
1
0
1
0
1-5 mA
0
1
1
0
0-20 mA
0
0
1
1
4-20 mA
0
1
1
1
Manual
input signal
DIL-switch position
1
2
0-5 V
0
0
0-10V
1
0
1.25 V - 6.25 V
0
1
1.25 V - 11.25 V
1
1
4.5.1 I n p u t t y p e
The input signal type is configured with Switches 1 to
4.
In tables 4.3 to 4.6, 1 indicates the lowered switch position.
• External input (external signal)
Table 4.3
• Manual input (external potentiometer)
The manual input range depends on the automatic input configuration.
Table 4.4
4-22
451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com