455-461 Series
4.5.2 Control (General)
Figure 4.3 shows the wiring diagram of the control and electronic power supply. Terminal
14
(current limit) is only used for the
461
series.
The analogue control input can be in voltage or in current.
The
"Auto"
position corresponds to the remote control or a controller, for example. The
"Manual"
position corresponds to the control by a potentiometer connected between terminal
12 (+10 V) and terminal 6 (0 V) or to a 0-10 V external voltage.
If the external current limit (by external setting potentiometer or by voltage) is not used, it is
essential to connect terminal 12 to terminal 14 directly (as indicated as a dotted line in
figure 4-3).
9 Ph 1 9 N or Ph 2
Installation
protection and
cut-off
device
+ 0
Input
0
OV
=
— -E=}— —
0.5 A
fuses
10 k1
External current —4/3
limit
4 -Auto"
+10V
Inhibition
2
3
5
10
1
13
14
15
16
Load
461 or
455
series
unit
MEM
Earth
Figure 4.3 Drive wiring diagram
For the 455 series, the "External limit" function is not available
Line
4-12
451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com