455-461 Series
4.5.10 "Slave" output
The logic signal (10 Vdc ; 10 mA) available between terminals 13 and 6 (0 V) is used to drive
static contactors.
The capacity of this output is characterized by the number of "Slaves" as follows:
• one 451 series contactor, standard input, or
• four 451 series contactors, parallel TTL inputs, or
• four 451 series contactors, serial "Multi-inputs".
Note
The following low level inputs / outputs:
- control signal
- load current image output
- load voltage image output
- "Slave" control output
- inhibition
are isolated (by transformers) from the supply voltage and
the power part.
4-20
451-461 User Manual