5
1.3
Step 1: Installation
This controller is intended for permanent
installation, for indoor use only, and enclosed in an
electrical panel.
Select a location which is subject to minimum
vibrations, where the ambient temperature is within
0 and 55
o
C (32 - 131
o
F) and humidity 5 to 95% RH
non condensing.
The controller can be mounted on a panel up to
15mm thick.
To ensure IP65 and NEMA 4 front sealing against
dust and water, mount on a non-textured surface.
Please read the safety information in section 3
before proceeding. The EMC Booklet part number
HA025464 gives further installation information.
1.3.1
Panel Mounting the Controller
1. Prepare a cut-out in the
mounting panel to the
size shown. If a number
of controllers are to be
mounted in the same
panel observe the
minimum spacing shown
2. Fit the IP65 sealing gasket behind the front
bezel of the controller
3. Insert the controller through the cut-out
4. Spring the panel retaining clips into place.
Secure the controller in position by holding it
level and pushing both retaining clips forward.
5. Peel off the protective cover from the display.
45 mm - 0.0 + 0.6
1.77 in -0.00, +0.02