Issue 2,   Nov-98.  Applies to software versions 1.3 & 1.4                           -8-                                                                                         HA026270

C

ONFIGURING THE 

C

ONTROLLER

Select configuration level to change: 

The type of control  

The

display units  

The input sensor type

  The scaling of linear inputs

The alarm configuration 

 The passwords.

To select configuration level

.

      Instrument Configuration

Instrument
Configuration

Options

Description

 

Display units

Centigrade

Fahrenheit

Kelvin

 

None

Decimal places

    

None

in display

    

One

    

Two

Control type

PID Control

 

On/off Control

Converts the controller
to an alarm unit

Control action

Reverse (normal action
for temperature control)

Direct (output
decreases as PV falls
below SP)

Manual reset
tracking (PD

In Auto holds manual
reset value

control)

In Auto tracks output for
bumpless A/M transfer

Input Configuration

Sensor Input

Options

Meaning

 

Input type

J thermocouple

K thermocouple

L thermocouple

R thermocouple

B thermocouple

 

N thermocouple

T thermocouple

S thermocouple

  

Platinell II

100

 Pt thermometer

!

Linear mV

Custom input(C=default)

"

Cold junction

Automatic

compensation

0

°

C external reference

(only appears

#$

45

°

C external reference

for TC inputs)

$

50

°

C external reference

Linear input scaling (Range -12 to +80mV)

%

mV input low

%

mV input high

!&

Displayed value
low

!

Displayed value
high

%

Sensor break

Off (Linear inputs only)

input impedance

1.5K

5K

15K

,

Alarm Configuration

The 

 list configures the three internal ‘soft’ alarms and causes

the appropriate alarm message to be flashed in the HOME display.

At this stage the alarm is indication only (known as a ‘soft alarm’).
To make the alarms operate the relay or logic outputs, follow the
instructions under “Relay and Logic input/output Configuration.

Alarm

Type

Meaning

 '

Alarm 1

The alarm is disabled

(

Full Scale Low alarm

(

Full Scale High alarm

Deviation band alarm

Deviation high alarm

Deviation low alarm

)

Alarm latching

 

Non-latching

*

Latched with automatic*
resetting.

 

Latched with manual*
resetting.

Alarm blocking

 
*

No blocking

Blocked until first good

The above sequence is repeated for:

  

 

(Alarm 2) and

 

 +

 

(Alarm 3)

,

Alarm setpoint

Limited by display range

limits

 

Limited by setpoint limits

*Automatic resetting means that, once the alarm has been
acknowledged, it will automatically clear when it is no longer true.
*Manual resetting means that the alarm must first clear before it
can be reset.

 Having selected a list heading, press 

 to select a parameter

       within a particular list. Press  

 and  

   to change the setting.

Press  

 or 

 to select 

Press 

 to reach the Access List Heading.

 Press

 

Press  

 or 

 to enter the password.

The factory default is 1.  

   will be

displayed when the correct password
has been entered.

 Press

 Press

Press  

 or 

 to enter the

configuration level password.  The
factory default is 2.  

   will be

displayed when the correct password

Press 

  to step across the configuration list headings.

 Press to enter configuration level.

% ,

% ,

!

!

mV

Displayed value

Содержание 2116

Страница 1: ...e latching ears click back into place to maintain the IP65 sealing Output ratings Logic Output 9Vdc 12mA non isolated from sensor input Used for Heating Cooling or Alarm Relay Output 2A 264V ac resistive Used for Heating Cooling or Alarm Contact Closure Input replaces Logic Output Used for Alarm Acknowledge or Timer start reset Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16...

Страница 2: ... TO ADJUST THE REQUIRED TEMPERATURE SETPOINT Press and release quickly the or button The setpoint will be displayed for 2 seconds TO VIEW THE DISPLAY UNITS Press and release quickly the or button The display units will be flashed for 0 5 sec If you get lost pressing and together will always return you to the HOME display If at any time no key is pressed within 45 seconds the display will always re...

Страница 3: ...ge setpoint limits and access the in built timer Change input and output limits TO ADJUST THE ALARM SETPOINTS TRIP LEVELS Alarm setpoints are found under the list Press twice to choose the list Note The other parameters listed on pages 4 and 5 are accessed and adjusted in exactly the same way as this example Keep pressing to select more list headings eventually returning to the HOME display This i...

Страница 4: ...larm type setpoint limits Alarm 3 Setpoint Full Scale Low Full Scale High Deviation Deviation High Deviation Low Alarm Hysteresis to in display units This value is common to all alarms Hysterisis is used to prevent the alarm output chattering by setting a difference between the alarm switch ON and switch OFF points Loop Break Time to minutes Home List Alarm List Autotune List PID 2 List Setpoint L...

Страница 5: ...o seconds Cold Junction Temperature measured at rear terminals Read only Millivolt Input measured at the rear terminals Read only Process value Offset to display units Calibration Password to User Calibration Enable Re instates factory calibration Re instates user calibration Low Calibration Point to display units Low Point Calibration Offset to display units High Calibration Point to display unit...

Страница 6: ...ill switch to standby mode The MAN beacon will light and will be flashed in the main display The process will cool down The timer will remain indefinitely in this state until reset When Reset will stop flashing The controller will return to reset in standby mode It can be returned to automatic control by setting the parameter in the HOME list to Mode 2 Dwell No Switch Off High alarm 2 has been sel...

Страница 7: ...art when is within 1 o C of the target setpoint TO START AND RESET THE TIMER There are two methods Method 1 This is the simplest method to control the timer Press until you reach the list Press until you reach the parameter time remaining TIP Promote to the HOME list for quick access as described in To Hide Revealing and Promote Parameters As soon as a value is entered into timing will commence wi...

Страница 8: ...larm Configuration The list configures the three internal soft alarms and causes the appropriate alarm message to be flashed in the HOME display At this stage the alarm is indication only known as a soft alarm To make the alarms operate the relay or logic outputs follow the instructions under Relay and Logic input output Configuration Alarm Type Meaning Alarm 1 The alarm is disabled Full Scale Low...

Страница 9: ...ions can be added to the relay or logic output by repeating steps 4 5 and 6 above Two decimal points will appear in those functions that has been added to the output Continued in the next column To Clear Alarms from an Output 1 Press until to reach 2 Press or to select 3 Leave for 2 seconds The display returns to which disconnects all alarms from the relay Passwords Passwords Range Default Full an...

Страница 10: ...ons together to return to the HOME display The display will flash to indicate that tuning is in progress 4 The controller will induce an oscillation in the temperature by turning the heating on and then off 5 After two cycles of oscillation the tuning will be completed and the tuner will switch itself off 6 The controller will then calculate the tuning parameters and resume normal control action I...

Страница 11: ...n these instructions is subject to change without notice While every effort has been made to ensure the accuracy of the information Eurotherm Controls shall not be held liable for errors contained herein Unpacking and storage The packaging should contain the controller with two panel retaining clips and this instruction leaflet If the packaging or the controller are damaged do not install the prod...

Страница 12: ...oming detached from the process thermocouple wiring becoming short circuit the controller failing with its heating output constantly on an external valve or contactor sticking in the heating condition Where damage or injury is possible we recommend fitting a separate over temperature protection unit with an independent temperature sensor which will isolate the heating circuit Please note that the ...

Страница 13: ...Issue 2 Nov 98 Applies to software versions 1 3 1 4 13 HA026270 ...

Отзывы: