45
601-000147 Rev. Y
Arch. 5105
25/02/2016
NEW OID
The same 2 numbers as the last in the slot OID.
In this way the pointed OID will be 1.3.6.1.4.1.19222.1.9.NEW OID
For example the line 8 in figure 1 points to 1.3.6.1.4.1.19222.1.9.2.4, i.e. to slot OID 1.3.6.1.4.1.19222.1.2.4
FORMAT
This is the data type used for the OID.
The supported formats are OCTECT_STRING, INTEGER and BOOLEAN.
If you select the BOOLEAN type:
in GET operation integer “1” is returned if the variable is equal to TRUE COND, “0” otherwise.
in SET operation if you send integer “1” the variable is set to TRUE COND, if you send “0” it is set to FALSE
COND.
TRUE (1) COND
This is the condition used for "true" in case of BOOLEAN type.
Write NULL for OCTECT_STRING and INTEGER types.
For example the line 13 in figure 1 uses BOOLEAN format with "Locked" as TRUE COND; in this case if you do a
GET operation on OID 1.3.6.1.4.1.19222.1.9.3.4, the returned integer will be "1" if the variable
1.3.6.1.4.1.19222.1.3.4 is "Locked", "0" otherwise.
Referring to line 16 in figure 1, in SET operation if you send the integer “1” to OID 1.3.6.1.4.1.19222.1.9.3.7, the
variable 1.3.6.1.4.1.19222.1.3.7 will be set to “On”; if you send “0”, it will be set to “Off”
FALSE (0) COND
This is the condition used for the "false" in case of BOOLEAN type.
Write NULL for OCTECT_STRING and INTEGER types.
SCALE
This is the scale factor for float/integer conversion.
It is used with INTEGER data type.
Write 1.0 for OCTECT_STRING and BOOLEAN types.
In GET operation the returned integer value is:
((int) (FLOAT_VALUE/SCALE)) + OFFSET
for example if you do a GET on 1.3.6.1.4.1.19222.1.9.1.26 (line 6 in figure 1) and the variable
1.3.6.1.4.1.19222.1.1.26 is FLOAT_VALUE=32.3, the value 32.3/0.1=323 will be returned (OFFSET=0).
In SET operation the value that will be really set is:
INTEGER_SET_VALUE*SCALE
for example if you want to set -12.3 on the variable 1.3.6.1.4.1.19222.1.3.10 (line 18 in figure 1), you have to do a
SET operation on 1.3.6.1.4.1.19222.1.9.3.10 with the INTEGER_SET_VALUE=-123; in this way will be set the float
value -123*0.1=-12.3
OFFSET
Doing GET operation, this value is add to the returned value after scaling.
TRAP
This field is used for enable (YES) or disable (NO) the traps generation.
TRAP THRESHOLD
This is the threshold used for trap generation.
For OCTECT_STRING and BOOLEAN data types a trap is generated when the OID value changes in and out from
the string specified in this field.
For INTEGER data types a trap is generated when the variable crosses (in both directions) the specified scaled
threshold.
IP TRAP DEST
This is the IP address the trap will be sent to.
TRAP GROUP
This is the number specified after the enterprise number (19222 for Eurotek) in the OID that will be sent for the trap.
TRAP NUMBER
This is the specific trap number that will be sent for the trap; it is specified in the Enterprise OID after the TRAP
GROUP.
For example if the oid 1.3.6.1.4.1.19222.1.1.26 (line 4 of figure 1) crosses 700*0.1=70, a trap will be sent to the IP
192.168.1.140 with the following Enterprise OID 1.3.6.1.4.1.19222.1.9.5000.102
DESCRIPTION
Field used for general description and notes
Содержание EK-MFR/2
Страница 1: ...1 601 000147 Rev Y Arch 5105 25 02 2016 User Manual System ALL4DIGIT EK MFR 2 ...
Страница 9: ...9 601 000147 Rev Y Arch 5105 25 02 2016 1 1 EK MFR 2 BLOCK SCHEME ...
Страница 18: ...18 EK MFR 2 25 02 2016 Arch 5105 601 000147 MN Rev Y Tabella 5 1 Indoor version Set up Table ...
Страница 26: ...26 EK MFR 2 25 02 2016 Arch 5105 601 000147 MN Rev Y Power Loop Configuration With EK AMH 6EK PWS X EK PSI ...
Страница 66: ...66 EK MFR 2 25 02 2016 Arch 5105 601 000147 MN Rev Y ...