WARNING

The DFI needs to be earthed and the power supply should have 
a residual current disconnection (RCD). An incorrect earth 
connection can lead to electrical shocks.

WARNING

Do not alter internal wiring.

CAUTION

Do not install the DFI at a location with potential explosion 
hazard.

WARNING

The DFI is for indoor use only.

INSTALLATION OF THE DFI

Read this information carefully and proceed step by step!

The pictures/drawing in this manual are for reference only.

5.1 Device 

• 

Select a position that is free from obstruction for the air flow

• 

Take care of the weight of the DFI and select a location where noise 
and vibrations do not cause nuisance

REMARK

Depending of the settings of the DFI noise and vibrations 
will increase.

5.2 General 

• 

Make sure that the supporting construction and anchorage are 
sufficient for the selected location

• 

Check local regulations with regard to installation

• 

Always select an easy accessible mounting location for  
easy maintenance.

ATTENTION

The DFI will require extra parts for installation. 

Mount a construction rail at the appropriate location.
Use sliding nuts with eye bolts to position the DFI exact level.
When the DFI has to be lowered significantly with regard to the mounting 
rail, place the mounting eyes further apart to create a bigger square. In this 
way the DFI will hang more stable.

A =  

Chain

B =  

Eye bolt

C =  

Lock plate

D =  

Slide nut

E =  

Rail

REMARK

Select mounting materials that can support the weight of  
the DFI.

E

D

C

B

A

ELECTRICAL INSTALLATION

Safety precautions with regard to the electrical installation:

• 

Do not install the DFI in an unsafe situation (regarding the electrical/
mechanical part)

• 

The supply voltage has to be within range of 200 – 270 Volts AC, single 
phase.

• 

Connect the remote control cables according to the wiring diagram in 
this manual.

• 

All wiring has to comply with local/national legislation and European 
wiring norm and may only be performed by authorized staff. 

REMARK

The supply voltage has to correspond to the nominal voltage 
mentioned on the type label of the DFI.

REMARK

The power supply has to be able to deliver a minimum wattage 
as mentioned at the typelabel of the DFI.

6.1 Power Supply

The power connection to the DFI is made with a 3 pole female CEE 
connector. The cable need to be of type H07RN-F. The size need to minimum 
1,5 sqmm. For short connections and 2,5 sqmm. for longer connections.

6.2 Control cable

The DFI can be controlled with the optional Touch Control DFI (partnr. 
1180442300) or Remote Control (partnr. 0010010310). All units, including 
control are connected in a “RS485 bus configuration”. 

Start point for the bus is the touch control/remote control and the end point 
is the (termination) resistor in the “last” DFI. 

REMARK

All DFI's are equipped with the bus (termination) resistor. This 
resistor need to be removed if the DFI is used in multiple unit 
setup except for the resistor in the last DFI.

Содержание DFI AIR CLEANER

Страница 1: ...EN Installation manual DFI AIR CLEANER Hanging unit with fine dust filter...

Страница 2: ...r page of this document This publication is to be used for the standard model of the product of the type given on the cover page Thus the manufacturer cannot be held responsible for any damage resulti...

Страница 3: ...mage is originating from proceedings that deviate from this installation manual or neglect Always wear the appropriate personal protection like safety goggles inhalation protection ear protection glov...

Страница 4: ...B Eye bolt C Lock plate D Slide nut E Rail REMARK Select mounting materials that can support the weight of the DFI E D C B A 6 ELECTRICAL INSTALLATION Safety precautions with regard to the electrical...

Страница 5: ...from partnr 1180456230A shows a setup with 3 devices For exact functionality consult the manual of the Touch Control DFI and device 7 2 RC MSA Cabling This is a 4 core unscreened cable The connection...

Страница 6: ...flow 4500m3 hr SW6 5 Fixed flow 5000m3 hr SW6 6 Fixed fan speed 3000m3 hr SW6 7 Fixed fan speed 3500m3 hr SW6 8 Fixed fan speed 4000m3 hr SW6 9 Fixed fan speed 4500m3 hr 8 3 Remote RC MSA A Dipswitch...

Страница 7: ...ion SW6 4 No valid selection SW6 5 No valid selection SW6 6 No valid selection SW6 7 No valid selection SW6 8 No valid selection SW6 9 No valid selection These settings for use with a touch control DF...

Страница 8: ...gn changes 05032020 0 Euromate enables people to breathe pure air For the improvement of indoor air quality we offer high quality contemporary products that effectively remove a broad range of polluta...

Отзывы: