NB: This system always guarantees the fumes evacuation, also in case of missed electric tension
Connection with multiple junctions
Connection that is exclusively done in cases of particular disadvantages in positioning. In this case, the
horizontal section must have a minimum slope of 3% upwards and must not exceed 3 meters, the vertical
section that goes from the stove to the second curve must be at least 1.5 meters long. The T inspection, at
the base, can also be applied inside the house (preferably external). If there is a fireplace, it must have a
preferably circular internal section; the square or rectangular sections must have rounded corners with a
radius of at least 20mm, the rectangular sections, with a maximum ratio of 1.5 between the sides, must have
a constant internal section, free and independent; at the base there must be an inspection hole. Always
verify a minimum forced draught of 10Pa and follow the regulation UNI 10683.
NB: In case of obstruction of the pipe, due to damages, or birds’ nest, the stove will stop (see the alarms
section) and it will be necessary to clean or repair the pipe, and ventilate the room as quickly as possible,
otherwise, it will saturate with smoke.
NB: The cleaning of the pipe should be done annually.