System Manual Safety Switch CES-AP-C.2-CH
17
Typical system times
Ready delay: After switching on, the unit carries out a self-test. The system is
ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment
when the actuator is at the operating distance (safety door closed) to moment
when the safety outputs switch on T
on
is 400 ms.
Risk time according to EN 60947-5-3: If an actuator moves outside the op-
erating distance, the safety outputs OA and OB are deactivated after a maximum
of 60 ms.
Difference time: The safety outputs OA and OB switch with a slight time offset.
They have the same signal state at the latest after a difference time of 10 ms.