Operating Instructions
Non-Contact Safety Switch CES-AP-C01-…
16
(translation of the original operating instructions) 112663-05-03/15
10. Setup
10.1. LED indicators
LED
Color
State
Significance
STATE
Green
illumi-
nated
Normal operation
flashing
- Teach-in operation or power up
- Actuator in limit range (from V0.1.2)
(refer to chapter
5. System status table on page 18
for further signal functions)
DIA
Red
illumi-
nated
- Internal electronics fault
- Fault at the inputs/outputs
10.2. Teach-in function for actuator (only for unicode evaluation)
The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
During a teach-in operation, the safety outputs and the monitoring output OUT are switched off, i.e. the system is in the
safe state.
Important!
Ì
The teach-in operation may be performed only if the device functions flawlessly. The red DIA LED
must not be illuminated.
Ì
The safety switch disables the code of the previous actuator if teach-in is carried out for a new
actuator. Teach-in is not possible again immediately for this actuator if a new teach-in operation is
carried out. The disabled code is released again in the safety switch only after a third code has
been taught.
Ì
The safety switch can only be operated with the last actuator taught.
Ì
If the switch detects the actuator that was most recently taught when in teach-in standby state,
this state is ended immediately and the switch changes to normal state.
Ì
If the actuator to be taught in is within the operating distance for less than 60 s, it will not be acti-
vated and the most recently taught in actuator will remain saved.
10.2.1. Preparing device for the teach-in operation and teaching in actuator
1. Apply operating voltage to the safety switch.
¨
A self-test is performed for approx. 0.5 s. After this, the LED flashes cyclically three times and signals that it is in
standby state for teach-in.
Standby state for teach-in remains active for approx. 3 minutes.
2. Move new actuator to the read head (observe distance < S
ao
).
¨
Teach-in operation starts, green LED flashes (approx. 1 Hz). During teach-in, the safety switch checks whether the actuator
is a disabled actuator. Provided this is not the case, the teach-in operation is completed after approx. 60 seconds, and
the green LED goes out. The new code has now been stored, and the old code is disabled.
3. To activate the new actuator code from the teach-in operation in the safety switch, the operating voltage to the safety
switch must then be switched off for min. 3 seconds.