background image

2

ATTENTION: 

Please read this manual carefully before using Etna Electronic Thermal Relay 

1. Product Details

ETNA Electronic Thermal Relay offers protection based on the programmed limits for current value 
and switch number. It is a protection element with single pole and electronic current control, which 
is exclusively designed for starting electric motors. It measures the drawn current with an internal 
current transformer within the relay or an external current transformer within the panel used for high-
powered motors, and enables instant monitoring of the current with the integrated 7-segment LED 
display. It notifies the operating and error status with LED lamps and dry contacts. The error history 
can be monitored, the low and high current limits , the maximum number of switches allowed per 
hour , the delay time based on low and high current limits can be adjusted, the low and high current 
automatic reset programs can be enabled or disabled using the menu. The parameters can be set 
easily using 'Up, Down' and 'Set' buttons.

Two versions of Etna electronic thermal relay are available.
1- ETR – DT

 (Electronic thermal relay with internal current transformer): In this version, the current 

transformer is included in the relay and it is designed to measure and provide protection in the 
applications ranging from 0 to 25 Amperes.

2- ETR – HT

 (Electronic thermal relay with external current transformer): This version is designed to 

measure and provide protection in the high current applications ranging from 10 to 300 Amperes via 
the current transformer externally placed in the panel.

Figure 1. ETNA Electronic Thermal Relay - External View

ETR – DT

ETR – HT

Error Warning Led

Set and Menu Button

Down Button

Up Button

On Warning Led

7 Segment Display

Содержание ETR-DT

Страница 1: ...Electronic Thermal Relay Product Introduction and Operation Manual...

Страница 2: ...number of switches allowed per hour the delay time based on low and high current limits can be adjusted the low and high current automatic reset programs can be enabled or disabled using the menu The...

Страница 3: ...he menu and save the adjusted parameters On LED Green LED lights up when ETNA electronic thermal relay is on or on relay is activated Error LED Red LED lights up along with an error code on LED displa...

Страница 4: ...High Current EYA failure is triggered error LED lights up and error relay is activated 5 Menu Figure 2 Main Screen Figure 3 Password Screen Figure 4 Error History Program Screen Figure 5 High Current...

Страница 5: ...s reset automatically in increasing intervals of 2 8 18 32 and 50 minutes respectively once Low Current error is triggered If low current is received at the end of the 5th automatic reset EbL error is...

Страница 6: ...the password screen by pressing the Set button enter the password using the Up Down buttons and check the error history in the PAG program Manually test the current drawn by the motor check the curren...

Страница 7: ...ON L N L DI 21 DI 22 N 31 32 41 42 ERROR ETR DT 0 25 A OUTPUT INPUT ON ERROR A SET START POWER OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT POWER INPUT START INPUT ETR...

Страница 8: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye Istanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr Rev 06 2021...

Отзывы: