2. General Specifications

•  0 - 25A measurement range with internal current transformer (ETR-DT)
•  10 - 300A measurement range with external current transformer (ETR-HT)
•  Password protection against unauthorized interventions
•  User-friendly, easy-to-use menu
•  3-digit / 7-segment LED display
•  8-bit microprocessor-based design
•  Operating frequency: 16Mhz
•  Operating voltage: 220V 50Hz AC
•  Operating temperature: -10 … +50°C
•  Net relay weight: 150g
•  Protection class: IP20
•  7 configurable parameters
•  Measuring current and monitoring on LED display
•  On and Error status LEDs
•  On and Error dry contact relay outlets
•  Adjustable low and high current limit values
•  Adjustable delay time based on low and high current protection
•  Adjustable maximum number of switches allowed per hour
•  Enabling/disabling low and high current automatic reset programs
•  Monitoring all error codes on LED display
•  Tracking old error codes via error history menu

3. Front Panel Description

•  Up / Down Buttons: 

 Used to navigate in the menu on LED display and to increase/decrease the 

numerical values. Moreover, the device can be manually reset by pressing and holding 'Up/
Down' buttons simultaneously for 2 seconds.

•  Set Button:

 Used to access the menu and save the adjusted parameters. 

•  On LED:  

Green LED lights up when ETNA electronic thermal relay is on or “on” relay is activated.

•  Error LED: 

 Red LED lights up along with an error code on LED display when one of the activated 

programs such as Low Current, High Current, Number of Switches is triggered. After the failure, 
if there is an active automatic reset program for low/high current failure and the electronic relay 
receives the 'start' command, red LED flashes to indicate that the error will be reset automatically 
and the electronic motor will start after the set delay time. If there is no active automatic reset 
program, red LED continuously lights up until the error is reset manually. If there an active 
automatic reset program but the electronic relay does not receive the 'start' command, red LED 
continuously lights up until the end of the period defined in the automatic reset program. The 
error is reset automatically at the end of this period and red error LED is turned off, waiting in 
standby until the 'start' command is received. While the error LED is on, the 'error' relay remains 
active.

4. Maintenance

Disconnect the power before maintenance and use the required personal protective 

equipment.

•  Etna electronic thermal relay must be checked for any loose electrical connections.
•  Ensure there is no abrasion, puncture or color change resulting from heating in the electrical 

cables.

Содержание ETR-DT

Страница 1: ...Electronic Thermal Relay Product Introduction and Operation Manual...

Страница 2: ...number of switches allowed per hour the delay time based on low and high current limits can be adjusted the low and high current automatic reset programs can be enabled or disabled using the menu The...

Страница 3: ...he menu and save the adjusted parameters On LED Green LED lights up when ETNA electronic thermal relay is on or on relay is activated Error LED Red LED lights up along with an error code on LED displa...

Страница 4: ...High Current EYA failure is triggered error LED lights up and error relay is activated 5 Menu Figure 2 Main Screen Figure 3 Password Screen Figure 4 Error History Program Screen Figure 5 High Current...

Страница 5: ...s reset automatically in increasing intervals of 2 8 18 32 and 50 minutes respectively once Low Current error is triggered If low current is received at the end of the 5th automatic reset EbL error is...

Страница 6: ...the password screen by pressing the Set button enter the password using the Up Down buttons and check the error history in the PAG program Manually test the current drawn by the motor check the curren...

Страница 7: ...ON L N L DI 21 DI 22 N 31 32 41 42 ERROR ETR DT 0 25 A OUTPUT INPUT ON ERROR A SET START POWER OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT POWER INPUT START INPUT ETR...

Страница 8: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye Istanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr Rev 06 2021...

Отзывы: