CHANNEL SCALING TAB
This tab shows the current calibration/scaling parameters for the input.
Each analogue channel has the resolution of 4096 steps.
Example:
We have a temperature sensor, specified to give 1000 mV at 10 °C and 2000 mV at 20 °C. If
we are using an analogue channel configured for 0-2500 mV, this corresponds to the steps
0-4095.
We therefore have:
10 °C -> 1000 mV -> step 1638
20 °C -> 2000 mV -> step 3276
Set the calibration parameters:
•
Unit = degC
•
Y1 = 10
•
Y2 = 20
•
X1 = 1638
•
X2 = 3276
Apply these settings by clicking "Set A/D cal values".