Internal Dip Switches
SWITCH
DESCRIPTION
MODULE
SW1
Not used
SW2
OFF= Ch 2: DI (default high, dry contact to ground or
LL<0.5V, HL>2.5V), AI (0 to 2.5V), Pulse in, DO (0 or
3.3V, 10uA)
ON= Ch 2: AI 4-20 mA
SW3
OFF= Ch 3: DI (default high, dry contact to ground or
LL<0.5V, HL>2.5V), AI (0 to 2.5V), Pulse in, DO (0 or
3.3V, 10uA)
ON= Ch 3: AI 4-20 mA
SW4
OFF= Ch 4: DI (default high, dry contact to ground or
LL<0.5V, HL>2.5V), AI (0 to 2.5V), Pulse in, DO (0 or
3.3V, 10uA)
ON= Ch 4: AI 4-20 mA
SW5
OFF= Ch 2: DI (Default high, dry contact or ground or
LL<0.5V, HL>2.5V, AI (0 o 2.5V) Pulse in, DO (0 or 3.3V,
10uA) or AI 4-20 mA depending on SW2
ON= Ch 2 will have extra hard pull up at 10k. SW2 need to be
OFF.
SW6
OFF= Only allowed state.
ON=
Not allowed, this risk CPU damage!
SW7
OFF= Ch7: DI (default high, dry contact to ground or
LL<0.5V, HL>2.5V), AI (0 to 2.5V), DO (0 or 3.3V, 10uA).
ON= Ch 7: AI 4-20 mA
SW8
Not used