. System malfunction warning 

Fault 
indication 

Failure cause 

Solutions 

” 

Temperature sensor open 
circuit or short circuit 

” 

Water flow sensor open circuit 
/short circuit 

” 

It is detected that water flow 
sensor is over limit 

1. Check whether the plug loose or not and 
whether cable is damaged or not. 
2. If plug and cable are intact, please replace the 
mainboard. 
3. If changing the mainboard is still invalid, 
please replace heaters. 
 

” 

It is detected that inside the 
heater, the temperature 
reaches 118 

 / 48 

 or 

much higher. 

” 

It is detected that inside the 
heater, the temperature 
reaches 110

/43.5

 or 

much higher. 

1. Check whether environmental temperature is 
over high. 
2. Check whether filter is blocking or just 
replaced. 
3. Check whether the metering valves and 
circulating pump are normal or not. 

” 

The water flow inside the 
heater is possibly too low. 

” 

It is sure that the water flow 
inside the heater is not 
enough. 

1. Check whether filter is blocking or is just 
replaced. 
2. Check whether the metering valves and 
circulating pump are normal or not. 
3. If the above is normal, please turn off the 
power supply for 15 seconds, then turn on the 
power and reset the system. 

” 

It lacks of water or water level 
is not reaching. 

” 

There is no water or not 
enough water for water level. 

1. Please check whether the water level is 
reaching the normal level or not. 
2. Please check whether all the cables about the 
water probe is normal or not. 

” 

Working current of light is 
over limit. 

Whether the interface of LED light (12VAC) or 
Ozone is short-circuit or not. 

” 

The current of circulating 
pump is oversize. 

Check whether the circulation pump is jammed 
to cause the flow stream. 

 

Other operation information 

1. “

”: It detected that it is going to freeze and it is starting to anti-freeze. 

2. “

”: Complement water system is working and other functions can be normal operation. 

3.  “

”:  Complement  water  system  is  pause  working  and  other  functions  can  be  normal 

operation. 

 

Содержание KL6600

Страница 1: ...er Mode 2 Plug and play mode is to get easy operation and easy installation 3 24 hours clock display and setup of circulation cleaning 4 Max 3KW of the heater water temperature display and the setting...

Страница 2: ...over voltage if it is beyond 260VAC then LED shows In these two kinds of situation the system will not go into normal operation Under this circumstance that the input voltage is normal the system woul...

Страница 3: ...ton and hold until it appears some icons or enters to a certain status 4 Click pressing means to click the button and let go right now within a second Working Mode 1 When A1 ON there is without neithe...

Страница 4: ...ice filtering antivirus cycle every day But it is only able to set the start time for the first filtering antivirus cycle And the second filtering cycle is automatically added it will starts after 12...

Страница 5: ...7 7 If the current water temperature shows 98 but the real water temperature is 100 At the moment as long as to adjust the fine tuning number for 2 the showing temperature will turn into 100 1 2 3 4...

Страница 6: ...sturizing function and at this time there is with 12 V power output of LED ON With moisturizing function B4 OFF Only with 1 surfing pump ON With 2 surfing pump note 1 The setting of all the jumpers is...

Страница 7: ...r temperature is reaching 46 7 8 or above all the heaters and circulating pumps stop working The operation of auto moisturizing B3 ON 1 When the water level pin detects that there is no water LCD show...

Страница 8: ...Installation structure KEY_DIS SENSOR A OZONE 220V 12VAC 1A 250V HT48R06A 1 LIGHT HT46R23 WCS2705 WCS2705 ON 1 2 3 4 5 6 7 8 ACN P1 P1L BLOWER ACN AUX ACN ACL ACN ACN ACN HT1 HT2 KL6600 ACN P1L Fig 8...

Страница 9: ...ure that the water flow inside the heater is not enough 1 Check whether filter is blocking or is just replaced 2 Check whether the metering valves and circulating pump are normal or not 3 If the above...

Страница 10: ...240V Compression strength 1250V 1 minute Not being punctured Insulation resistance 200M Waterproof level IPX5 Electric shock preventing 1 class 2 Maximum output load index Heater 4KW 220 240VAC Surfi...

Отзывы: