KL6600
www.ethink-spa.com
5
5. At the initial stage of each filtering cycle, all the devices will run for 15 seconds to purify the
pipeline equipment. Ozone starts to work 15 seconds later.
In order to prolong the service life of anti-virus system, every 15 minutes ozone stops working
for 15 minutes.
When any surfing pump (or high speed pump) and blower is power on, the anti-virus system
will stop working at once.
Ⅶ
).Temperature Adjust:
Press and hold “
” to enter to the setting mode, and continuously pressing “
to
enter to Temperature fine-tune mode(Fig.6).At this moment, press “
” and“
” can
change the fine tuning number, adjusting range is -7
~
7
℉
。
If the current water temperature shows 98
℉
, but the real water temperature is 100
℉
.At the
moment, as long as to adjust the fine-tuning number for 2
℉
, the showing temperature will turn
into 100
℉
.
1 2 3 4 5 6 7 8
A
ON
1 2 3 4
B
ON
Fig.7.Switchbank A
Ⅷ
).The Main Board Specifications and DIP jumpers settings (Fig.7)
A1
:
OFF: With work mode switch and filter function.
ON: Without filter function, “
” is to control the heater ON/OFF.
A2
:
OFF: With Economy mode.
ON: Without Economy mode.
A3: OFF: With filtering antivirus cycle artificially.
ON: Filtering antivirus cycle built-in is unchanged. It starts to work at 14:00, and it works for
3 hours.
***Note***
Only when A1=OFF, A2 and A3 are effective.
A4: OFF: Display Fahrenheit temperature.
ON: Display Celsius temperature.
A5: OFF: Surfing pump 1 for a single-speed pump.
ON: Surfing pump 1 for a double-speed pump.