MANUAL SGM700
42
The following screen will be visible:
In
dAC 6
you set the
weigher end value
for the analog output. At this value the analog
output stops with its maximum value. Press key 2 < 2sec. to enter dAC 6.
Fill in the wanted end value using key 1 and key 2. Key 1 is for changing the number
(1-9), key 2 is for changing the position of the cursor. Confirm by pres- sing key 3 >2
sec.
Increase Decrease
Left
Right
Confirm
The following screen will be visible:
In
dAC 7
you set
analog output mode
. Press key 2 < 2sec. to enter dAC 7. Scroll thru the
weigher function options pressing key 1 and select which analog output mode is needed
by pressing key 3 >2sec. (options are: 1-5).
Increase Decrease Confirm
Options are:
1 RAW
Register value 65535 parts
2 0-24mA
input value 0 to 24 mA will be calculated from 0 to 100,00%
3 0-20mA
input value 0 to 20 mA will be calculated from 0 to 100,00%
4 4-20mA
input value 4 to 20 mA will be calculated from 0 to 100,00%
5 4-24mA
input value 4 to 24 mA will be calculated from 0 to 100,00%