26
W1 Installation Manual
Configure the W1 CC Emergency Driver TEST Button for
Low-Voltage Loads
The W1 Emergency Driver "TEST" button is configured by default to work with Navis 100 Fixed
White and Fade to Warm luminaires. If you are using third-party loads with less than 30
V forward voltage, you must set the W1 CC Emergency Driver test switch to work with low-
voltage loads. TheW1 CV Emergency Driver "TEST" button does not require configuration.
Locate the switch block"S4 Emergency Shift" (see the illustration on
). The switch block
has four switches, one for each output.
•
Leave the switch for each output in the default "OFF" (30 V) position to allow the "TEST"
button to work with Navis 100 Fixed White and Navis 100 Fade to Warm luminaires and
other loads with 30 V or higher forward voltage.
•
Set the switch for each output to "ON" (15 V) to allow the "TEST" button to work with loads
with less than 30 V forward voltage.
Complete the Installation
Now that you have completed wiring the power to your emergency system driver, you can
complete the standard installation procedures. Refer to
to complete
the following steps after wiring the Sense and Maintained inputs.
•
DMX In and Thru Connections on page 17
•
Connect Luminaires to Outputs on page 19
•