Purge SV Solenoid Valve control

The instrument eSelect M – CD COOL offers

two modes

for purge operations (water drain) of the SV.

TIMER mode:

for easy programming or in case of conductivity probe fault, the operator may enable the Timer mode; the SV is driven by the

internal timer regardless of the conductivity reading in the cooling tower.

P

u

rg

e:

T

IM

E

R

m

o

d

e

Mode Selection

Selects the operational mode to drive the purge SV: the two modes are via

Timer

built into the instrument

or via the

Conductivity

measurement.

Cycle time

Selects the intermediate time between two purge operations.

Cycle duration

Selects the opening cycle of the purge SV.

Flow Sensor

Enables or disables the Flow sensor function (proximity probe).

Max Manual Time

Overwrites the previous SV programming (timer or conductivity), selecting the maximum SV opening time
and manual start-up(next step). It isasafety measure inthecasewheretheoperator openstheSVvia
the Max manual programming and forgets to close it.

Manual ON / OFF start-up

Supersedes the previous Max Manual Time programming and SV programming (timer or conductivity).
The operator manually selects when the SV is ON and OFF. "Manual ON / OFF start-up" only works if the
previous function" Max Manual Time" has been programmed.

CONDUCTIVITY mode:

processes the conductivity level to control purge operations; the displays show the measured EC values and drives the

relay output connected to the SV solenoid valve. Electroconductivity is monitored by a setpoint: once this is reached, the instrument commands
solenoid valve opening and drains the desalinated and conditioned water. NOTE: for EC conductivity measurements, the display shows μS
values up to 1999 (micro Siemens), then they change automatically into mS (milli Siemens) above the value of the latter

.

C

O

N

D

U

C

T

IV

IT

Y

M

O

D

E

Mode Selection

Selects the operational mode to drive the purge SV: the two modes are via

Timer

built into the instrument

or via the

Conductivity

measurement.

High Setpoint

Sets the setpoint at the highest value, after reaching which the relay closes (opens the SV)

Low Setpoint

Sets the setpoint at the lowest value, after reaching which the relay opens (closes the SV)

Max opening time

Maximum opening time of the purge valve: it is a safety mode that replaces the conductivity measurement
in the event of EC probe fault or other defects.

Max Alarm

If the EC measurement exceeds the selected

Max

value, the relay is closed andthe alarm message is

displayed. The alarm isindependent ofthechosendirection (direct / reverse), viarelay 4,it controls an
external signalling device.

Min alarm

If the EC measurement is below the selected

min

value, the relay is closed and the alarm message is

displayed. Thealarm isindependent ofthe chosendirection (direct / reverse), viarelay 4,it controlsan
external signalling device.

Direction

Direct

,theoutput isactivewhenthemeasuredvalue islowerthantheselectedsetpoint.

Reverse

,the

output is active when the measured value is higher than the selected setpoint

Flow Sensor

Enables or disables the Flow sensor function (proximity probe).

Max Manual Time

Overwrites the previous SV programming (timer or conductivity), selecting themaximum SV openingtime
and manualstart-up(next step). It isasafety measureinthecasewheretheoperatoropenstheSVvia
the Max manual programming and forgets to close it.

Manual ON / OFF start-up

Supersedes the previous Max Manual Time programming and SV programming (timer or conductivity).
The operator manually selects when the SV is ON and OFF. "Manual ON / OFF start-up" only works if the
previous function" Max Manual Time" has been programmed.

ON-OFF mode:

The unit features an ON-OFF mode which activates (or deactivates in the event of reverse mode ON) the output relays

connected to the ON-OFF equipment such as SV (solenoid valve).

RELAY 4 ON-OFF RELAY OUTPUT:

The relay 4 output may be connected to the alarm device (buzzer or light) or to other equipment.

ADVANTAGES: increases safety measures providing an alert if the parameters are out of control.

MIN / MAX ALARM:

The

Alarm

function makes it possible to select the minimum and maximum values outside which the instrument goes into alarm mode.

To restore the alarm function, wait for the measurement to go back to the setpoint

ADVANTAGES: increases the safety measures assuring an alert if the parameters are out of control.

PROGRAMMING FUNCTIONS

Содержание eSelect M 1 CD COOL

Страница 1: ...OPERATING INSTRUCTIONS AND MAINTENANCE IT UK eSelect M 1 CD COOL UNI EN ISO 9001 2008...

Страница 2: ...ent 9 General features 9 Main features 9 Dimensions of the instrument 9 Main additional functions 10 Wall installation 12 Diagram of electrical connections 12 Control Panel 14 ON OFF mode 16 DIRECT RE...

Страница 3: ...OR OF THE CONDUCTIVITY PROBE 21 TEMPERATURE settings 22 DATE AND TIME Timer in real time 22 PURGE operations by means of internal TIMER programming 23 PURGE operations by means of CONDUCTIVITY measure...

Страница 4: ...NDUCTIVITY 34 CONDUCTIVITY sensors Configuration and MEASUREMENT RANGE 35 Configuration of CONDUCTIVITY PROBE wires 36 Installation of LEVEL PROBES and TANKS for chemical products 36 Suggestions for t...

Страница 5: ...istributor Intended use of the device The device must be solely employed for the use it has been expressly built for i e to check the pH Rx measurement Any other use is considered improper and therefo...

Страница 6: ...or any industrial conditioning system The controller is able to interact with other process equipment such as a range of conductivity sensors based on the measurement range flow meters drain solenoid...

Страница 7: ...urement range and K factor cell constant K1 Range up to 20 00 mS Hysteresis PWM start up point 500 S Resolution 10 S K5 Range up to 2 000 S Hysteresis PWM start up point 50 S Resolution 1 S K5 Range u...

Страница 8: ...g pump voltage free relay 5Amax 230VAC RELAY 5 output BIOCIDE2 ON OFF metering pump voltage free relay 5Amax 230VAC AUX Output ALARM voltage free contact relay 5A max 230Vac FLOW sensor Blocks outlet...

Страница 9: ...sting operation Install the unit in a dry place away from heat sources Max room temperature40 C Strictly comply with the regulations in force in the various countries regarding electricalsystems Fit t...

Страница 10: ...g Meter IN 3 Proximity Sensor input BLACK wires Proximity Sensor input BLUE wires 12VDC 12 VDC output of the Proximity Sensor BROWN wire 4 20 mA1 Proportional output Conductivity 4 20mA1 for metering...

Страница 11: ...ire BLACK wire Not Connected REMEMBER unit with universal voltage 100 250 VAC 10 or 9 24VDC If the real voltage is constantly at the limit minimum or maximum or when the peaks are far above the mentio...

Страница 12: ...ity INHIBITOR TANK when the Inhibitor tank reaches a low level closed contact BIOCIDE1 TANK when the Biocide1 tank reaches a low level closed contact BIOCIDE2 TANK when the Biocide2 tank reaches a low...

Страница 13: ...to adjust the setpoints in ON OFF mode and is used to enable or disable the output relays when the selected hysteresis is achieved Hysteresis is useful when there are too many quick swings around the...

Страница 14: ...amming START UP DELAY The start up delay stops the output relays when the unit is switched on thus allowing the sensor to polarise assuring correct measurements programmable FLOW SENSOR function Proxi...

Страница 15: ...s opens the SV Low Setpoint Sets the setpoint at the lowest value after reaching which the relay opens closes the SV Max opening time Maximum openingtimeofthepurgevalve itis asafetymodethat replacesth...

Страница 16: ...nual ON OFF start up SupersedesthepreviousMaxManualTimeprogrammingandSVprogramming timerorconductivity The operator manuallyselectswhentheSV isONand OFF Manual ON OFFstart up onlyworks if the previous...

Страница 17: ...the biocide activation time Time lock Output time lock mode SV purge inhibitor dispensing and Biocide2 dispensing operations are blocked for the duration of the Biocide1 dispensing operations thus pre...

Страница 18: ...and editing selects the step of the menu or increases decreases the value ESC goes back to the previous menu or does not save the change Press OK to start To go forward quickly press and hold one of t...

Страница 19: ...The value is set by the user 0 100 C in the configuration menu it is the reference parameter for offsetting the pH value Automatic The value measured by the PT100 probe is the reference parameter for...

Страница 20: ...onductivity level to control purge operations the displays show the measured EC values and drive the relay output connected to the SV solenoid valve Electroconductivity is monitored by a setpoint once...

Страница 21: ...of CONDUCTIVITY measurement Processes the conductivity level to control purge operations the displays show the measured EC values and drive the relay output connected to the SV solenoid valve SV PURGE...

Страница 22: ...ring pump Menu Selection INHIBITOR INHIBITOR MENU Mode Selection Disabled NOTE by selecting Disable it is not possible to program the INHIBITOR The instrument eSelect M CD COOL offers four modes for i...

Страница 23: ...upersedes the previous Max Manual Time programming and SV Manual Start up programming timer or conductivity The operator manually selects when ON the SV is ON and OFF Manual ON OFF start up only works...

Страница 24: ...been programmed Press to go back to or press to go back to INHIBITOR METERING operations via TIMER programming function The Timer controls inhibitor dispensing operations via the internal timer at the...

Страница 25: ...o process the input digital contact Selects the inhibitor dispensing time INHIBITOR MENU Flow Sensor Enables or disables the Flow sensor function proximity probe The flow Enabled sensor is useful in t...

Страница 26: ...1 00 Start time h s 10 30 The program in biocide mode entails many steps that may be Start time h s 10 30 Enabl days Mo N programmed to assure more accurate metering operation with Enabl days Mo N Tue...

Страница 27: ...thus preventing awaste ofthechemical productwhileallowingits 0 S disinfection cycle to be completed at the same time BIOCIDE MENU BIOCIDE MENU Flow Sensor Flow Sensor Enables or disables the Flow sen...

Страница 28: ...t usea portableECinstrumentorsamplesolutionshavingknownvalues toensuretheconductivitylevelmatchestherequirements Use a conductivity sensor with maximum cable length 3 4 m MEASUREMENT When calibration...

Страница 29: ...s in the Purge menu SETTING 4 20mA Measurement 20 00 m S Press to go back to or press to go back to Program the date and time by selecting the backlit steps Flow Sensor if there is no water flow in th...

Страница 30: ...ess Modbus Address from 0 to 254 38400 192 168 1 100 Modbus Baudrate transmission speed EXPERT MENU EXPERT MENU TCP Address IP address The above menus are ONLY displayed if the instrument of the eSele...

Страница 31: ...e user may adjust the desired K factor IMPORTANT the conductivity ranges described above are only indicative considering that for example a K1 probe range 20 mS is able to perform fair measurements be...

Страница 32: ...length 3 m Weight 135 gr Cell constant K Range K1 standard 20 mS 20 000 S Model STEC K5 Code 99210009 Electrodes AISI 316 Pressure 8 bar Max Body PTFE Cable length 3 m Weight 137 gr 135 gr Cell const...

Страница 33: ...re no changes Conductivity levels are NOT stable Check again using a portable instrument especially the temperature The signal from the sensor does not change Repeatsensorcalibrationandiftheproblemper...

Страница 34: ...ntactor Furthermore ETATRON recommends installing a UPS genset to assure continuity thus ensuringnodataarelost Asystemthatissetupwithoutfollowingtheproperelectricaldesignrules withoutanearthing system...