FUNCTIONS
ACCESSORIES OF THE PLUS PUMP
In order to facilitate the consultation of this manual, the configuration with the function described is shown in the
subsection titles. Nothing is specified when the function is common to all versions.
Remote Control - Level - Proximity (Instrument versions only)
Remote control means the ability to remotely control any device by means of a cable, in our case bipolar; which means
that through the opening and closing of a contact, placed at a maximum distance of 100 metres, we can enable or disable the
delivery of the impulses generated by the electronic circuit. You can choose between two different operation modes from the
menu:
DIRECT
Contact open pump operating, contact closed pump in stand-by.
REVERSE
Contact open pump in stand-by, contact closed pump operating.
By connecting a floating sensor to the connector of the remote control you can control the level of the additive metered
by the pump.
In the case of the control pump, it is possible to activate the input for connection to the proximity sensor which detects
the passage of the flow in the probe holder and enables the operation of the pump.
Flow rate per impulse (proportional versions only)
For accurate metering in the eOne Plus pump the option to both manually and automatically set the flow rate for each
injection has been implemented by starting the procedure laid down in the appropriate configuration menu, in this case, the
electronic device, performs independently the necessary calculations for the proper calibration of the injection.
Setting the maximum frequency
Depending on the model the metering pump exits from the production line with a specific maximum injection frequency,
if necessary, the user can change this parameter by lowering or restoring it in accordance with the needs of the plant to be
treated.
PPM Scale setting
Depending on the type of probe installed, you can select the measurement scale, the ranges available are the following:
0
2 ppm
0
10 ppm
0
20 ppm
0
200 ppm
This setting is valid in both the PPM and Cl configuration.
Alarms
See the next chapter for a detailed description of the different alarms available.
Clock
In some applications, there may be the need to program the activation or deactivation of the pump, which is why the
electronic device is equipped with a clock and calendar. The following settings can be carried out:
CLOCK
hh:mm
–
Day (Hour:minutes
–
MON/TUES/WED/THU/FRI/SAT/SUN)
DATE
Day/Month/Year.
During normal operation of the pump the time will always be present on the display.
Password
By means of enabling and setting the 4-digit password, the user can protect the device and prevent access to the
programming menus by unauthorized personnel.