Heating circuit
Adjusting the heating curve
SH Operation
Adjusting the heating curve for outside
temperatures above 0°C -> Changing
"Flow at +10°C"
If the heating circuit is always too cold or too warm
in the
transition period
, the flow temperature
"Flow at +10°C"
is
increased or reduced
.
No large jumps in temperature
For underfloor heating, never more than 2°C
For radiators, never more than 4°C
Press
to open the text menu for the selected
heating circuit.
Tap the [Heating circuit] line and, in the submenu,
tap the [Heating curve] line.
Double-tap on the [Flow at +10°C] line (or select
the line and press the [Change value] button).
2
x
A settings screen opens:
Enter the new flow temperature for this heating
circuit. Press [Accept] to save the new value.
The text menu for the selected heating circuit is
displayed. Press
to open the "Heating circuit"
overview.
Adjusting the heating curve for outside
temperatures below 0°C -> Changing
"Flow at -10°C"
If the heating circuit is always too cold or too warm
in winter
, the flow temperature
"Flow at -10°C"
is
increased or reduced
.
No large jumps in temperature
For underfloor heating, never more than 2°C
For radiators, never more than 4°C
Press
to open the text menu for the selected
heating circuit.
Tap the [Heating circuit] line and, in the submenu,
tap the [Heating curve] line.
Double-tap on the [Flow at -10°C] line.
2
x
A settings screen opens:
Enter the new flow temperature for this heating
circuit. Press [Accept] to save the new value.
The text menu for the selected heating circuit is
displayed. Press
to open the "Heating circuit"
overview.