PROGRAMS
Set the
PROGRAM
Connet power supply cable and start the pump with ON/OFF key.
Led will be on the last program set (default setting: ).
In OFF mode led will blink once every 2 seconds on the last program set (default setting: ).
Start/shutdown
PROGRAMMING THE PUMP
• Keep pressed P for 4 seconds.
• Leds blink together.
• Press P.
• Press SCROLL and choose a program.
• Press P to confirm. Led will be on the program set.
If you do not press any key, after 30 seconds pump will esc from programming mode.
Each program has its own led.
Tab. 6. Programs menu
PROGRAMS
WORKING MODE
mA
1
proportional dosing mode based on mA current signal
CONSTANT
constant dosing mode
CONSTANT / DIVIDE
costant dosing mode with pulses divider (to reduce up to 10 times
pump capacity)
MULT 1÷10
1
External pulses from a water meter are multiplied by a factor “N” from 1
to 10. Set “N” value turning DIVIDER MULTIPLIER FACTOR ADJUSTMENT
KNOB (grey labelled scale N: 1-10).
DIV 1÷10
1
External pulses from a water meter are divided by a factor “N” from 1 to
10. Set “N” value turning DIVIDER MULTIPLIER FACTOR ADJUSTMENT
KNOB (grey labelled scale N: 1-10).
DIV 10÷100
1
External pulses from a water meter are divided by a factor “N” from 10 to
100. Set “N” value turning DIVIDER MULTIPLIER FACTOR ADJUSTMENT
KNOB (grey labelled scale N: 1-10).
Grey labelled scela 1-10 is proportional to the range 10-100.
Adjust the knob on maximum value (10) is equivalent to setting the
scale on 100.
DIV 100÷1000
1
External pulses from a water meter are divided by a factor “N” from
100 to 1000. Set “N” value turning DIVIDER MULTIPLIER FACTOR
ADJUSTMENT KNOB (grey labelled scale N: 1-10).
Grey labelled scale 1-10 is proportional to the range 10-100.
Adjust the knob on maximum value (10) is equivalent to setting the
scale on 1000.
1
Not available on K CO PLUS and K CL PLUS models.