28
www.eta.co.at
Requirements
Electrical connections
5
Electrical connections
5.1
Requirements
Electrical connection must only be made by
qualified specialist personnel
The electrical installation must only be performed
by specialist personnel with the corresponding
qualifications.
Requirements
Observe the standard and special regulations of local
power supply companies.
For full separation according to the setup require-
ments, a separating device of overvoltage
category III must be installed in the permanent
electrical installation. In most cases, these require-
ments are fulfilled with a circuit breaker, for example.
For speed-controlled pumps (controled via PWM-
signal), the maximum cable lengths of the pump
manufacturer must be observed.
Potential equalization is needed for the boiler
The boiler must be connected to the potential equaliza-
tion of the boiler room or the building. Country-specific
regulations must be observed.
DANGER!
Electric shock
There are live parts on the circuit boards. If
touched, they can cause injury and
property damage.
Before beginning any work, isolate the system
completely from all power sources, ensure that it
cannot be switched back on, and verify that it is
safely isolated from supply.
CAUTION!
Flexible stranded conductors
If flexible stranded conductors are not used for the
wiring, the contacts in the plug connections will be
subjected to excessive mechanical strain. In this case,
the warranty for the electronics would become null and
void.
Only flexible stranded conductors may be used for
the wiring.
Maximum outputs
Maximum line length for temperature sensor
The maximum line length for the electrical
connection of the temperature sensor is 20 m.
Connection diagrams
Fig. 5-1: Analogue input
Fig. 5-2: Digital switch
Mains protection
C 13
Mains connection
3 x 1.5²
Type of supply cable
H05VV-F 3G 1.5
230 VAC components:
1.0²
Temperature sensors:
0.5² - 1.0²
230 V output
Maximum
power
A single output
250 W
Sum of all outputs
700 W
Potential-free output
(special function)
Maximum
switching capac-
ity
A single relay output
500 W