3.3 H
EATING
AND
HOT
WATER
OPERATION
MODES
Both heating and the hot water can be prepared in several modes.
The meaning of the modes is analogical to both cases and it is presented in the table.
SYMBOL
NAME
DESCRIPTION
comfort
The comfort temperature is maintained all the time.
time
Works according to the time limit.
economic
The ecomomy temperature is maintained all the time.
turned off
The circuit is turned off. Only protection functions work.
3.4 H
EATING
To enter the heating menu on the main screen, press
buttons ''10'' or ''11''.
There are current and set temperatures, as well as the
mode, displayed on the screen.
Also symbols for currently working system elements are
visible.
3.4.1 SETTINGS
NAME
DESCRIPTION
Comfort temperature [
°
C]
Set temperature in the room in the comfort range, with the time mode or the
comfort mode.
Economical temperature [
°
C]
Set temperature in the room in the economic range, with the time mode or the
economic mode.
Hysteresis [
°
C]
The accuracy of maintaining the set target temperature in the room. It may also
affect the frequency of the boiler inset. If the hysteresis is higher the burner turns
on with lower frequency for a longer period of time.
Room sensor calib. [
°
C]
Calibrating the chosen sensor.
Work mode
Chosen operating mode of the circuit.
HC temp. set manually [
°
C]
Set temperature for the instalation when the weather steering is not chosen.
Temp. HC for -20
°
C [
°
C]
Set temperature for the instalation when the outside temperature is below -20
°
C
Temp. HC for 0
°
C [
°
C]
Set temperature for the instalation when the outside temperature is below 0
°
C
Temp. HC for 10
°
C [
°
C]
Set temperature for the instalation when the outside temperature is above 10
°
C