Chapter 3. Detailed description of screens/functions
3.1 B
OILER
3.1.1 SET TARGET TEMPERATURE AND OPERATING MODE
Boiler target set temperature and operating mode can be
regulated after pressing number ''6'' on the main screen.
The following table presents available boiler operating modes.
SYMBOL
NAME
DESCRIPTION
manual
The boiler temperature is set directly by the user. The boiler works to maintain the
set target temperature.
automatic
The boiler temperature is set automatically on the basis of the current need of the
heating circuits, hot water circuits or the buffer.
When there's no need to heat the water, the temperature will be set to minimum
of 7°C (antifreeze mode), and the boiler will turn on only when needed.
time- manual
The boiler temperature is set as in the manual mode, but the boiler can work only
in set time limits.
time- automatic
The boiler temperature is set as in the automatic mode, but the boiler can work
only in set time limits.
3.1.2 SETTINGS
NAME
DESCRIPTION
Set temperature [°C]
The set temperature in manual or time manual mode.
Switching hysteresis [
°
C]
The burner is turned on when the temperature in the boiler is lower than the set
temperature, minus the switching hysteresis.
Hysteresis exemption [
°
C]
The burner is turned off if the temperature in the boiler is higher than the set
temperature plus hysteriesis exemption.
10
www.estyma.pl
EGP -EN 20171024