AIR TO WATER HEAT PUMP SYSTEM

INSTALLATION AND SERVICE MANUAL

6

EN

3.5

A drain cock must be fitted below the water cylinder in the inlet pipework. It must

be sited between the water cylinder and the Check Valve.

3.6

A sanitary circuit expansion vessel may be fitted to the cold water supply as

shown in Diagram 2 to prevent wastage of expanded water. The following sizes

are recommended:

150 litre

12 litre vessel

210 litre

18 litre vessel

300 litre

24 litre vessel

3.7

A re-circulation circuit can be installed on the sanitary water circuit. A connection

is provided for the re-circulation circuit return pipe (threaded G3/4 female).

3.8

The primary heating circuit

MUST

be connected via the Hydro Unit. Refer to the

Installation Instructions supplied with the Hydro Unit for full details.

4.0

ELECTRICAL REQUIREMENTS

4.1

The unit is supplied with a factory fitted cylinder heater complete with thermal

sensor and over-temperature cut-out. The cylinder heater is rated 2.75kW at

230V~.

4.2

The cylinder heater is located behind the white terminal cover on the front of the

unit. The cover is secured by 2 screws on each side of the cover and a threaded

domed nut on the front of the cover.

ISOLATE THE ELECTRICAL SUPPLY

BEFORE REMOVING THE COVER

.

4.3

The cylinder heater

MUST

be earthed.

4.4

All electrical wiring should be carried out by a competent electrician and be in

accordance with the latest national Wiring Regulations. The circuit must be

protected by a suitable fuse and double pole isolating switch with a contact

separation of at least 3mm in both poles.

4.5

The cylinder heater should be wired in accordance with Diagram 3 and the Air to

Water Heat Pump Installation Manual. The supply cable must be via the Heat

Pump Controls Housing, direct connection to the mains electrical supply will

invalidate the guarantee and may result in a dangerous installation. The supply

cable must be routed through the right hand cable gland provided and the outer

sheath of the cable firmly secured by tightening the screw on the cable gland.

The recommended cable type is 2.5mm

2

3 core heat resistant sheathed.

4.6

The thermal sensor should be connected to the Heat Pump Controls Housing in

accordance with Diagram 3 and the Air to Water Heat Pump Installation Manual.

1

4

3

2

5

6

8

9

7

1

1

COLD WATER INLET

2

ISOLATING VALVE

3

SAFETY GROUP NF7 BAR

4

SANITARY WATER
EXPANSION VESSEL

5

DISCHARGE PIPE

6

PRIMARY CIRCUIT RETURN

7

PRIMARY CIRCUIT FLOW

8

HOT WATER OUTLET

9

SANITARY WATER
RE-CIRCULATION
CONNECTION

Diagram 2

Содержание HWS-1501CSHM3-E

Страница 1: ...SYSTEM INSTALLATIONS UND WARTUNGSANLEITUNG 26 DE SYST M TEPELN HO ERPADLA VZDUCH VODA SERVISN A MONT N MANU L 38 CZ CR LEVEG V Z H SZIVATTY RENDSZER FELSZEREL SI S SZERVIZEL SI K ZIK N 60 HU 72 GR LUF...

Страница 2: ...AL REGULATIONS PLEASE LEAVE THIS MANUAL WITH THE UNIT FOR FUTURE REFERENCE TECHNICAL SPECIFICATIONS Rated pressure 1 0 MPa 10 bar Test pressure hydraulic 1 5 MPa 15 bar Minimum recommended supply pres...

Страница 3: ...shcaft m b H Petersgasse 45 A 8010 Graz Austria Hungary Magyar AIRCOND Klimaanlagen Handelsgesellshcaft m b H Petersgasse 45 A 8010 Graz Austria Greece Carrier Hellas Aircondilioning S A 4g Andersen s...

Страница 4: ...nce 2 0 INSTALLATION GENERAL REQUIREMENTS 2 1 National Wiring Regulations may contain restrictions concerning the installation of these units in certain areas eg Bathrooms 2 2 The unit MUST be install...

Страница 5: ...ontinuously downward direction in a frost free environment 3 2 The water connections on the unit accept direct connection of 22mm outside diameter pipe nuts and olives are supplied for this purpose Th...

Страница 6: ...t on the front of the cover ISOLATE THE ELECTRICAL SUPPLY BEFORE REMOVING THE COVER 4 3 The cylinder heater MUST be earthed 4 4 All electrical wiring should be carried out by a competent electrician a...

Страница 7: ...inder for long periods without draw off will become de oxygenated and potentially corrode the vessel material If the installation is to be left unused following installation and commissioning the wate...

Страница 8: ...remove the thermal cut out sensing bulb from its pocket on the cylinder heater by pulling outwards Be careful not to kink the capillary tube 6 6 Remove the element tail insulating shroud by pulling it...

Страница 9: ...released 8 0 USER INSTRUCTIONS 8 1 The water storage temperature at the Air to Water Heat Pump System Water Cylinder is set at the control panel of the Hydro Unit This can be set to give temperatures...

Страница 10: ...correct parts are ordered 9 2 DO NOT replace with parts not recommended by the manufacturer as this will invalidate your guarantee and may render the installation dangerous 9 3 Description Part No Cy...

Страница 11: ...sor 1 Cylinder heater thermal cut out has operated 2 Faulty water cylinder temperature sensor 1 Water storage temperature on Heat Pump Controller is set too high 2 Faulty water cylinder temperature se...

Страница 12: ...ervice within a period of 7 days If this is not the case it must either be drained or regularly flushed as required in the section Commissioning Warning 11 7 The unit is NOT guaranteed against damage...

Страница 13: ...or the distributor In case of installation of a new product it may be possible to have the distributor pick up old WEEE directly The producer importer and distributor are responsible for collection a...

Страница 14: ...129 NOTES...

Страница 15: ...130 NOTES...

Отзывы: