BURNER FAILS TO START

BURNER FAILS TO START AFTER NORMAL OPERATION

POSSIBLE CAUSES

SITUATION

REMEDIES

Flame instability

Motor Runs

Check nozzles to burner head dimension

and electrode position

Incorrect head settings

Burner pre-purges

Check oil pressure

Low oil pressure

Adjust air damper

Excess air

Flame occurs

Check that photo cell is clean and unobstructed

Photo cell not seeing light

Burner locks out

Confirm with photo cell

Photo cell failed

Confirm with new control (NB. It is advisable to

change the photo cell if also changing control)

Control faulty

Motor runs

Check that photo cell is not

seeing ambient light

False light

Burner pre-purges

Check that H.T. leads are sound and are not

arcing other than at electrode gap

No spark

No flame occurs

Check oil supply to burner-

check that pump is not airlocked

No oil

Burner locks out

Check operation of magnetic valve.

Check or replace fuse if necessary.

Check reason for failure

Adjust thermostat

Reset overheat device, find reason

for it’s operation and rectify

Check by replacement

Fuse has blown

Appliance thermostat has not reset

Appliance overheat device has operated

Control relay or photo cell defective

Burner fails to start

Lamp not lit

Oil not being delivered

Excess flue draught is preventing

flame establishment

No spark

Burner runs to lockout

Motor runs

Check that oil tank, oil lines, fire valve, pump

and nozzle are all in good order

Rectify condition

Check ignition transformer. Check electrode gap

and porcelains

DELAYED IGNITION, BURNER STARTS VIOLENTLY

Recomission burner

Replace nozzle

Check and recomission

Check and rectify

Check and tighten

Check and replace

Check the electrode adjustment,

see diagram

Check electrodes for damage

Check H.T. leads for damage and disconnection

Excessive draught

Nozzle partly blocked

Oil pressure too low

Flue blocked or damaged

Fan slipping on shaft

Pump coupling loose or worn

Delayed ignition

Burner pulsates on start-up

only with hot flues

Burner pulsates - on start up

Burner starts violently

BOILER/COOKER FAULT FINDING CHART

16

Front of cooker

Baffle

Arrangement

Blanking plate

Flue box door

Boiler burner

combustion

sampling point

Cooker burner

combustion sampling

point

Flue box

sealing plate

and gaskets

Blanking plate

securing screws

Kicker strip securing

screws

Efficiency baffles

0-60 & 0-80 only

(not shown)

Blanking Plate - Fig.7

Sampling Points - Fig.8

Baffle Arrangement - Fig.9

Содержание O-106

Страница 1: ...lame Tube BFB 01 002 002 01 01 1001 D 0 60 BURNER Nozzle 0 6 x 80ES 2021 254 Flame Tube BFB 01 104 01 01 1010 2 COOKER BURNER Nozzle Danfoss 0 3 x 80 H or Delavan 02 02 1150 0 3 80 A Flame Tube BFB 01...

Страница 2: ...0 1 O 60 OC 36 000 Btu h 80 A or H 87 1 notch 4 5 O 106 170 4 41 O 80 130 3 62 O 60 100 2 96 MODEL AIR SUPPLY MIN TOTAL FUEL CONSUMP CM 2 l h MODEL OUTPUT INPUT Nozzle Pressure Fuel Air C02 Soot No kW...

Страница 3: ...e fitted to the programmer Commission the programmer as described in figs 3a 3b Typical systems are shown in Figs 4 5 5A 6 6A The water system and the electrical wiring system used must be in accordan...

Страница 4: ...em can allow the boiler and pump to operate on bypass only the bypass must be placed at least 1 5m 5 3 away from the boiler Inhibitor Attention is drawn to the current issue of BS5449 and BS 7593 on t...

Страница 5: ...is firing check and if necessary adjust oil pressure see Technical Data Carry out combustion checks by inserting probe into sampling point provided at the flue box Fig 8 The air setting is pre set at...

Страница 6: ...CentaurPlus controls are fitted with battery reserve which maintains programmed times in the event of a mains power failure Battery Reserve The battery must be commissioned prior to fitting the contr...

Страница 7: ...L Boiler stat Boiler burner Cooker programmer Cylinder stat L641A or equivalent DHWS Cylinder primary motorised valve 28mm V4043H or equivalent Heating circuit motorised valve V4043H or equivalent Roo...

Страница 8: ...1 L N E HORSTMANN C17 Model OC COOKER ONLY Fig 6a Boiler stat Boiler burner Cooker programmer Cylinder stat L641A or equivalent DHWS Cylinder primary motorised valve 28mm V4043H or equivalent Heating...

Страница 9: ...nce overheat device has operated Control relay or photo cell defective Burner fails to start Lamp not lit Oil not being delivered Excess flue draught is preventing flame establishment No spark Burner...

Страница 10: ...Tel No Fax No OFTEC Reg No Engineers Name Date Address Tel No Fax No OFTEC Reg No Engineers Name Date Address Tel No Fax No OFTEC Reg No 18 Engineers Name Date Address Tel No Fax No OFTEC Reg No Engin...

Отзывы: