- 11 - 

 

 

MAXIMUM MOTOR CURRENT

MAXIMUM MOTOR CURRENT

MAXIMUM MOTOR CURRENT

MAXIMUM MOTOR CURRENT    
Maximum operating current of the motor. 

Adjust in accordance with the motor's data plate, plus 10%. 
Note: This screen only appears in the initial preset or retrieving the factory settings 

 

NOMINAL PRESSURE

NOMINAL PRESSURE

NOMINAL PRESSURE

NOMINAL PRESSURE    
Configuration of the work pressure of the unit. 

CONFIGURATION OF THE STOP FREQUENCY

CONFIGURATION OF THE STOP FREQUENCY

CONFIGURATION OF THE STOP FREQUENCY

CONFIGURATION OF THE STOP FREQUENCY    

 

CALCULATED STOP FREQUENCY

CALCULATED STOP FREQUENCY

CALCULATED STOP FREQUENCY

CALCULATED STOP FREQUENCY    
The stop frequency is calculated automatically. 

Will be recalculated every time that is changed the nominal pressure. 

To set a value in the manual mode, press

 (Man) 

 

STOP FREQUENCY MANUALLY

STOP FREQUENCY MANUALLY

STOP FREQUENCY MANUALLY

STOP FREQUENCY MANUALLY    
Enter the desired stop frequency

Note: This value should only be entered by experts. 

ADDITIONAL PARAMETERS SETTING

ADDITIONAL PARAMETERS SETTING

ADDITIONAL PARAMETERS SETTING

ADDITIONAL PARAMETERS SETTING    

 

FINE ADJUSTMENTS

FINE ADJUSTMENTS

FINE ADJUSTMENTS

FINE ADJUSTMENTS 

To set additional parameters, press

 

 (Config) 

To complete the setup, press

 

 (Exit)    

 

DIFFERENTIAL PRESSURE

DIFFERENTIAL PRESSURE

DIFFERENTIAL PRESSURE

DIFFERENTIAL PRESSURE    
Configuration of the difference between the set and start-up pressure.  

For ex. : 3 bars set – 0.5 bars differential = 2.5 bars start-up 

 

STOP DELAY

STOP DELAY

STOP DELAY

STOP DELAY    
Timing of the unit before a stop. This timing process is associated to the stop 
frequency. 

 

REVESE ROTATION

REVESE ROTATION

REVESE ROTATION

REVESE ROTATION    
To check the motor rotation direction, press 

 (Check) 

To change rotation direction, press 

 (Change) 

 

Starting the motor, to 25Hz, for CHECK TURN DIRECTION 
Press

 

 ON, to activate the pump. 

Press

 OFF, to stop the pump. 

Press OK

OK

OK

OK to exit the screen. 

 

Confirm INVERT TURN. 
Change to "YES" to reverse the turn direction 

 

AUXILIARY PUMPS

AUXILIARY PUMPS

AUXILIARY PUMPS

AUXILIARY PUMPS    
For adjust auxiliary pumps parameters, press 

 (Adjust) 

If there are no regulated pumps, press 

 to advance to screen 11. 

Содержание SPEEDRIVE

Страница 1: ...SPEEDRIVE INSTRUCTIONS MANUAL INSTRUCTIONS MANUAL INSTRUCTIONS MANUAL INSTRUCTIONS MANUAL EN EN EN EN...

Страница 2: ...he pump or the installation TABLE OF CONTENTS TABLE OF CONTENTS TABLE OF CONTENTS TABLE OF CONTENTS 1 GENERAL INFORMATION 3 2 TECHNICAL SPECIFICATIONS 3 2 1 Models 3 2 2 Dimensions 3 2 3 Features 3 3...

Страница 3: ...his Manual can lead to motor overloads diminishment in technical characteristics reduction of the unit s working life and all types of subsequent results for which we decline any responsibility 2 TECH...

Страница 4: ...es are primed completely 3 2 Elect 3 2 Elect 3 2 Elect 3 2 Electrical connection to the motor rical connection to the motor rical connection to the motor rical connection to the motor 3 2 1 Speedrive...

Страница 5: ...inverter set DANGER Risk of electrocution Never open the Speedrive cover before disconnecting the power supply during at least 5 minutes least 5 minutes least 5 minutes least 5 minutes Figure 2 Figure...

Страница 6: ...e Three Three Three Phase Version Phase Version Phase Version Phase Version Prepare the motor wires with ferrites connect the grounding wire 2 Connect the motor wires to the provided socket 3 Single S...

Страница 7: ...size Motor size Motor size Motor size Leakage current Leakage current Leakage current Leakage current 0 75 to 3 kW 3 5 mA 4 to 5 5 kW 5 mA The electrical installation should have a multiple separatio...

Страница 8: ...used 5 Auxiliary transducer input Not used 6 Only in single phase versions 230 V potential output 2A maximum external display or acoustic operation for alarm signals 7 Micro switches used to configur...

Страница 9: ...equipped pumps point for equipped pumps Do not need any further adjustment Do not need any further adjustment Do not need any further adjustment Do not need any further adjustment Speedrive module pur...

Страница 10: ...ressure The pump will run automatically as needed To display parameters press View To return to the start screen press Menu MANUAL OPERATION MANUAL OPERATION MANUAL OPERATION MANUAL OPERATION It shows...

Страница 11: ...by experts ADDITIONAL PARAMETERS SETTING ADDITIONAL PARAMETERS SETTING ADDITIONAL PARAMETERS SETTING ADDITIONAL PARAMETERS SETTING FINE ADJUSTMENTS FINE ADJUSTMENTS FINE ADJUSTMENTS FINE ADJUSTMENTS T...

Страница 12: ...does not have to be determined since the circuit communications system detects its number DELAY ON DELAY ON DELAY ON DELAY ON Delay time between the activation of auxiliary pumps Avoid continuous star...

Страница 13: ...T PROPORTIONAL CONSTANT START PROPORTIONAL CONSTANT START PROPORTIONAL CONSTANT START PROPORTIONAL CONSTANT Allows the variation of the unit s proportional constant upon start up STAR INTEGRAL CONSTAN...

Страница 14: ...o the main screen 2 1 From any screen tap OK to return to the main screen 2 1 From any screen tap OK to return to the main screen 2 1 From any screen tap OK to return to the main screen 2 1 OVERCURREN...

Страница 15: ...m will stop when a short circuit is detected in the motor The reset is automatic If the error is not solved 4 new attempts are performed If the error is still present after the fourth attempt the syst...

Страница 16: ...rious Espa solutions for a multiple pump booster set control a Booster set with On Off auxiliary pumps equipped with ELV box b Booster set with inverter regulated auxiliary pumps equipped with Speedri...

Страница 17: ...rrent of the auxiliary pumps according to his motor s data plate plus 10 plus 10 plus 10 plus 10 All auxiliary pump motors should be of the same power CHANGE FREQUENCY CHANGE FREQUENCY CHANGE FREQUENC...

Страница 18: ...is done as described in this manual The connection of the pressure transducer must be made solely on the Master Speedrive A 2 wire twisted and shielded cable 0 5mm2 section must make the communication...

Страница 19: ...menu as follows MOTOR FREQUENCY MOTOR FREQUENCY MOTOR FREQUENCY MOTOR FREQUENCY Configuration of the nominal frequency of the motor 50Hz or 60Hz Check the motor s nameplate Note This screen only appea...

Страница 20: ...ELECTROMAGNETIC COMPATIBILITY Speedrive M1 and M2 are in compliance with directive 2004 108 CE electromagnetic compatibility for industrial environment For residential environment it will require the...

Страница 21: ...21 10 MENU DIAGRAM 10 MENU DIAGRAM 10 MENU DIAGRAM 10 MENU DIAGRAM...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...Cod 155854 Cod 155854 Cod 155854 Cod 155854 11 11 11 11 2010 05 2010 05 2010 05 2010 05 ESPA 2025 S L C Mieres s n 17820 BANYOLES GIRONA SPAIN www espa com...

Отзывы: