Parameter Display and Configuration via
CICT
CAN-CBM-DP
Software Manual Rev. 2.0
75
DP Byte
Absolute PLC peripheral address (decimal).
Parameter
DP Byte
can only be set or changed via the PROFIBUS side by means of the SIMATIC
Manager program and is only displayed, here.
Value range: 0 ... 127 (decimal)
Length
Number of data bytes of one frame transmitted on the CAN bus (decimal).
Parameter
Length
can only be set or changed via the PROFIBUS side by means of the SIMATIC
Manager program and is only displayed, here.
Value range: 1 ... 8, 16 (decimal)
CAN ID
CAN identifier which is to be linked to PLC address (hexadecimal).
If a PLC input port, i.e.
I/O
=input has been selected for the address, the CAN identifier for the CAN-
CBM-DP module is a reception identifier (RxId).
If a PLC output port, i.e.
I/O
=output has been selected for the address, the CAN identifier for the CAN-
CBM-DP module is a transmission identifier (TxId).
The CAN identifier can only be changed, if parameter
ConfigByDP
has the value
N
(see user parameter
list).
Value range: 0 ... 7FD hex, EEEE hex, FFEF hex
Format
Setting of byte assignment between CAN and PLC data regarding Intel and Motorola format
(hexadecimal).
Parameter
Format
will be described in detail on the following page.
Format
can only be changed, if parameter
ConfigByDP
has the value
N
(see user parameter list).
Value range: 00 ... FE hex
Type
Parameter
Type
depends on the setting of other parameters and is only used for information.
ConfigByDP
This parameter shows whether the module has last been configured via the PROFIBUS. Only if an
N
for NO is displayed, it is possible to change parameters
CAN Id
and
Format
via the configuration
program CICT. Otherwise (i.e.
Y
for YES) the configuration can only be changed via the PROFIBUS.