3.4.1.1 Station Status 1
Station status 1 contains error messages of the DP slave. If a bit is ‘0’, no error applies. A bit set to ‘1’
signalizes an error.
Bit
Error message if bit = ‘1’
Error handling
0
DP slave cannot be addressed by the
master
- correct PROFIBUS address set at the CAN-
CBM-DP?
- bus connector correctly wired?
- power supply available at CAN-CBM-DP?
- power off/power on executed at CAN-CBM-DP
in order to read in DP address?
1
DP slave is not yet ready for data
exchange
- wait until the CAN-CBM-DP has completed
start up
2
The configuration data transmitted
from DP master to DP slave do not
correspond to the DP slave structure.
- check whether the station type and the CAN-
CBM-DP structure have been correctly entered
via the configuration tool
3
The slave has got external diagnose
data.
- request and evaluate external diagnose data
4
The requested function is not being
supported by the DP slave.
- check projecting
5
DP master cannot interpret the
response of the DP slave.
- check bus structure
6
Wrong setting.
- evaluate diagnose bytes 9 and 10
7
DP slave has already been set by
another master.
- this bit is always ‘1’, if you, e.g., just access the
CAN-CBM-DP by means of a PG or another
DP master.
The PROFIBUS address of the setting master is
in the diagnose byte ‘Master-PROFIBUS
address’.
Table 3.4.3:
Bits of station status 1