Configuration via SIMATIC Manager
CAN-CBM-DP
Software Manual Rev. 2.0
27
Attention:
SYNC Time
can be set in three different ways:
1. As described above.
2. Via bytes 4 and 5 of the Communication Window (refer to page
37).
3. Via the configuration tool
CICT
(refer to page 73).
All three specifications are equal. That means that the last
specification is valid!
Note:
If the software is updated to a version
t
1.03, when using an
existing application program (older than 12/1999), the missing entry
of the configuration data would be interpreted as ‘0’, and the SYNC
and START functions would be deactivated, therefore.
5.1.3 Assigning the Slots of the DP Slave
The desired number of slots to be used by the
DP slave for data exchange is set by double
clicking the device ‘Universal Module’ for
each byte with activated DP-slave window.
In the DP-slave window the assigned slots are
represented by a ‘0’.
Fig. 5.1.3:
Setting the parameters