Overview
CAN-Control-I/O
Hardware Manual Rev. 1.3
6
1.2.3 Digital Inputs
Number
64
in groups with 8 inputs each
Input circuit
refer page 15
Inputs voltages
inputs voltage range:
max. permissible:
-30 V
#
U
IN
#
33 V
switching threshold input = '0':
U
IN
< 9 V
switching threshold input = '1':
U
IN
> 15 V
Input current
input = '1':
I
ON
= approx. 3.5 mA (typical, at 18 V)
I
ON
= approx. 10 mA (typical, at 30 V)
Circuit protection
electrical isolation by optocouplers,
each 8 inputs use one common GND
Filter
option: RC with
J
on[24V]
.
500 ns
Table 1.2.3:
Input specification