background image

 

G8872_1 Installation Manual AUS 

 

3

Error Codes: 

This gas fire has been designed to show error codes to help explain and identify any fault 
situation that occurs. 
These codes will appear on the wireless control in the form of a large letter “E” with a number 
beside it. Codes can normally be reset by turning the heater off then on again at the wall. 
The following table shows what each code means and possible ways to rectify the situation. 
 

Error Code 

Suggested action 

 
 
 
 
  
 

 

PCB Over Temp 

(Printed Circuit Board)  

 

 

 
IB600 -

 Usually associated with a four sided fascia being mounted too 

high resulting in an insufficient air gap between the lower removable strip 
and the bottom of the outer fascia. 

IB850 -

 Usually insufficient cavity ventilation. 

Note:

 This error has a 

permanent lock out and will require the unit to be reset 10 minutes after 
the initial error (turning the power to the fire off "at the wall" then on again 
after a few seconds). 

 
 
 
 
 

Flame Failure or 

Power Flue trip 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
The fire has tried to light three times and failed. 
- Check gas supply and check other gas appliances to see if they are 
affected. If you have two separate LPG cylinders, switch over to the full 
bottle or contact your gas supplier. You may need to retry igniting the fire 
a few times after re-establishing gas supply.  
 
- Check the electrode placement in relation to the flame. Ensure it is well 
enveloped in flame as per the diagram in the installation instructions. 
Ensure no coals have dropped onto the ignition electrodes between the 
burners. 
 
- Ensure the electrodes are not contacting any metalwork including the 
burners. 
-  Check that there has not been a significant reduction in pressure inside 
the house (such as an extractor fan in a nearby kitchen) which can pull 
flue gas back down through the firebox "snuffing" the flames.  

 
 
 
 
 

Draught Diverter 

Bimetallic Trip 

 

The bimetallic snap disk mounted on the hood of the draught diverter at 
the rear of the fire or on the lid of the fire has tripped. The possible causes 
for this could include... A gust of wind pushing exhaust gases back down 
the flue or a significant reduction in air pressure inside the house or cavity 
which is pulling exhaust gases back down the flue (such as a extractor fan 
in a nearby kitchen).  
If installed into a tight masonry cavity it may indicate that the whole 
installation is getting too hot and some additional ventilation into the cavity 
may be required. 
In the unlikely event that the fans have stalled, and the snap disk on the 
lid of the fire has tripped, this would show an E3 also. Simply check that 
the fans are running normally after resetting and running the fire again. 
 

Note:

 This error has a permanent lock out and will require the unit to be reset 10 minutes 

after the initial error (turning the power to the fire off "at the wall" then on again after a 
few seconds). 

Содержание IB600

Страница 1: ...ried out only by a suitably qualified and trained person Gas and electricity supply MUST be isolated before any service operation is carried out on this appliance This manual must be left with the app...

Страница 2: ...ents Page Error Codes 3 Cleaning the Log Set and Glass 5 Checking Operating Pressure 6 Removing Cleaning Fan 7 Removing Electronic Draw 8 Replacing a Wireless Control 9 Gas Type Conversion 10 Annual S...

Страница 3: ...ment in relation to the flame Ensure it is well enveloped in flame as per the diagram in the installation instructions Ensure no coals have dropped onto the ignition electrodes between the burners Ens...

Страница 4: ...gain after a few seconds Valve Temp Sensor Trip The valve temperature sensor has detected abnormally high temperatures around the valves This is an unlikely fault and should it occur please contact th...

Страница 5: ...eposition log set so that front edge of each log is just behind each row of holes in burner top Clear any blockage from primary air port of burner Check to make sure flue system is drawing well Step 1...

Страница 6: ...tallation pipe size or upstream regulator settings Replace inlet test point screw 3 Remove the operating pressure test point screw Connect manometer tube and measure pressure with heater running on fu...

Страница 7: ...THE FIRE BEFORE PROCEEDURE Remove front glass and log set as described on page 5 Step Two Remove fire box from heater by taking out the screws from each corner and Pulling fire directly outwards as sh...

Страница 8: ...ee wires connecting the electronics to the igniters and flame rod must be removed manually from the PCB Printed Circuit Board ISOLATE THE POWER TO THE FIRE BEFORE PROCEEDURE Step Two Take out the two...

Страница 9: ...tinguish the fire 4 Immediately after releasing the Aux On Off button turn on the remote control and wait four to five minutes During this time the fire will re ignite NOTE During this period the fire...

Страница 10: ...Step Three Unscrew rear burner clamp bracket On left side Lift out the rear burner Step Four Change the three jets with the jets supplied in kitset Replace the rear burner and clamp bracket Replace f...

Страница 11: ...dust from the cavity that houses the fan and solenoid valves and from the ducts down each side of the heater that lead to this cavity 8 Test all joints for gas tightness 9 Reassemble heater and check...

Страница 12: ...G8872_1 Installation Manual AUS 12 Wiring Diagram...

Отзывы: