Esam E1200 Скачать руководство пользователя страница 13

 

MANUALE D’USO / USER’S GUIDE

 

 



E1200 

[email protected]     www.esam.biz 

page 13 - 16 

rev. 1.07 

0714 

 

 

Register 

Type 

Read / Write 

Label 

Description 

Value / Unit 

2736 

Int 

Read/Write 

AOS41 

E3000 mod 4, out 1: selezione misura in uscita / 

output reading selection

  (

 6

100 ... 180 

2737 

Int 

Read/Write 

AOT41 

E3000 mod 4, out 1: tipo di uscita / 

output type

 

Tab. 7 

2738 

Int 

Read/Write 

AOI41 

E3000 mod 4, out 1: uscita normale - invertita / 

normal - inverted output

 

0-1 

2739 

Int 

Read/Write 

AOF41 

E3000 mod 4, out 1: funzione applicata all’uscita / 

function applied to output

 

Tab. 8 

2740 

Int 

Read/Write 

AOS42 

E3000 mod 4, out 2: selezione misura in uscita / 

output reading selection

  (

 6

100 ... 180 

2741 

Int 

Read/Write 

AOT42 

E3000 mod 4, out 2: tipo di uscita / 

output type

 

Tab. 7 

2742 

Int 

Read/Write 

AOI42 

E3000 mod 4, out 2: uscita normale - invertita / 

normal - inverted output

 

0-1 

2743 

Int 

Read/Write 

AOF42 

E3000 mod 4, out 2: funzione applicata all’uscita / 

function applied to output

 

Tab. 8 

2744 

Int 

Read/Write 

AOS43 

E3000 mod 4, out 3: selezione misura in uscita / 

output reading selection

  (

 6

100 ... 180 

2745 

Int 

Read/Write 

AOT43 

E3000 mod 4, out 3: tipo di uscita / 

output type

 

Tab. 7 

2746 

Int 

Read/Write 

AOI43 

E3000 mod 4, out 3: uscita normale - invertita / 

normal - inverted output

 

0-1 

2747 

Int 

Read/Write 

AOF43 

E3000 mod 4, out 3: funzione applicata all’uscita / 

function applied to output

 

Tab. 8 

 

 

 

 

 

 

2800-2801 

float 

Read/Write 

AOL11 

E3000 mod 1, out 1: inizio campo uscita / 

output low range

 

(

 7

)

 

2802-2803 

float 

Read/Write 

AOH11 

E3000 mod 1, out 1: fine campo misura / 

output high range

 

(

 7

)

 

2804-2805 

float 

Read/Write 

AOL12 

E3000 mod 1, out 2: inizio campo uscita / 

output low range

 

(

 7

)

 

2806-2807 

float 

Read/Write 

AOH12 

E3000 mod 1, out 2: fine campo misura / 

output high range

 

(

 7

)

 

2808-2809 

float 

Read/Write 

AOL13 

E3000 mod 1, out 3: inizio campo uscita / 

output low range

 

(

 7

)

 

2810-2811 

float 

Read/Write 

AOH13 

E3000 mod 1, out 3: fine campo misura / 

output high range

 

(

 7

)

 

2812-2813 

float 

Read/Write 

AOL21 

E3000 mod 2, out 1: inizio campo uscita / 

output low range

 

(

 7

)

 

2814-2815 

float 

Read/Write 

AOH21 

E3000 mod 2, out 1: fine campo misura / 

output high range

 

(

 7

)

 

2816-2817 

float 

Read/Write 

AOL22 

E3000 mod 2, out 2: inizio campo uscita / 

output low range

 

(

 7

)

 

2818-2819 

float 

Read/Write 

AOH22 

E3000 mod 2, out 2: fine campo misura / 

output high range

 

(

 7

)

 

2820-2821 

float 

Read/Write 

AOL23 

E3000 mod 2, out 3: inizio campo uscita / 

output low range

 

(

 7

)

 

2822-2823 

float 

Read/Write 

AOH23 

E3000 mod 2, out 3: fine campo misura / 

output high range

 

(

 7

)

 

2824-2825 

float 

Read/Write 

AOL31 

E3000 mod 3, out 1: inizio campo uscita / 

output low range

 

(

 7

)

 

2826-2827 

float 

Read/Write 

AOH31 

E3000 mod 3, out 1: fine campo misura / 

output high range

 

(

 7

)

 

2828-2829 

float 

Read/Write 

AOL32 

E3000 mod 3, out 2: inizio campo uscita / 

output low range

 

(

 7

)

 

2830-2831 

float 

Read/Write 

AOH32 

E3000 mod 3, out 2: fine campo misura / 

output high range

 

(

 7

)

 

2832-2833 

float 

Read/Write 

AOL33 

E3000 mod 3, out 3: inizio campo uscita / 

output low range

 

(

 7

)

 

2834-2835 

float 

Read/Write 

AOH33 

E3000 mod 3, out 3: fine campo misura / 

output high range

 

(

 7

)

 

2836-2837 

float 

Read/Write 

AOL41 

E3000 mod 4, out 1: inizio campo uscita / 

output low range

 

(

 7

)

 

2838-2839 

float 

Read/Write 

AOH41 

E3000 mod 4, out 1: fine campo misura / 

output high range

 

(

 7

)

 

2840-2841 

float 

Read/Write 

AOL42 

E3000 mod 4, out 2: inizio campo uscita / 

output low range

 

(

 7

)

 

2842-2843 

float 

Read/Write 

AOH42 

E3000 mod 4, out 2: fine campo misura / 

output high range

 

(

 7

)

 

2844-2845 

float 

Read/Write 

AOL43 

E3000 mod 4, out 3: inizio campo uscita / 

output low range

 

(

 7

)

 

2846-2847 

float 

Read/Write 

AOH43 

E3000 mod 4, out 3: fine campo misura / 

output high range

 

(

 7

)

 

 

 

 

TABELLA 4 / 

TABLE 4

 

 

TABELLA 5 / 

TABLE 5

 

Valore

 

Senso ciclico delle fasi 

 

Valore 

Selezione Media Misure 

Value

 

Voltage Phase Sequence 

 

Value 

Averaging mode selection 

 123 

Corretto / 

Sequence 

OK 

 

NM, misura eseguita ogni semiperiodo / 

NA, measure every half ac period 

 132 

Invertito / 

reverse sequence

 

 

Media aritmetica dei 2 ultimi semiperiodi / 

Arithmetic mean of last 2 half ac periods

 

 0 

Tutte fasi Off / 

All Phase Off

 

 

ME, costante di tempo circa 50 ms / 

EA, time constant about 50msec

 

 1 

Fase 3 on / 

Phase 3 on

 

 

ME, costante di tempo circa 100 ms / 

EA, time constant about 100msec

 

 10 

Fase 2 on / 

Phase 2 on

 

 

ME, costante di tempo circa 200 ms / EA

, time constant about 200msec

 

 100 

Fase 1 on / 

Phase 1 on

 

 

ME, costante di tempo circa 500 ms / EA

, time constant about 500msect

 

 11 

Fase 3+2 on / 

Phase 3+2 on

 

 

ME, costante di tempo circa 1000 ms / EA

, time constant about 1000msec

 

 101 

Fase 1+3 on / 

Phase 1+3 on

 

 

 

 

 110 

Fase 1+2 on  / 

Phase 1+2 on

 

 

 

 

 111 

3 Fasi on,senso indeterminato 

3 Phases on, Sequence error 

 

N.B. 

Dove: NM = Nessuna media; ME = Media Esponenziale

  

Where: NA =  No Average; EA = Exponential average

 

 

Содержание E1200

Страница 1: ...ccia Ethernet configurazione dello strumento e visualizzazione misure da browser Web acquisizione dati da sistemi Scada con protocollo Modbus TCP inserzione trifase con 3 TA o 2 TA ARON o monofase con 1 TA rapporti TA e TV configurabili montaggio su profilato DIN EN50022 35 The Network analyzer E1200 entirely designed and developed by ESAM is built to comply with all the modern requirements of mea...

Страница 2: ...attiva uscente Active Energy Out Ea Ea1 Ea2 Ea3 Wh Energia reattiva entrante Reactive Energy In Er Er1 Er2 Er3 VARh Energia reattiva uscente Reactive Energy Out Er Er1 Er2 Er3 VARh Potenza attiva media entrante ultimi 15 minuti Average Active Power In last 15 minutes Pm Pm1 Pm2 Pm3 W Potenza attiva media uscente ultimi 15 minuti Average Active Power Out last 15 minutes Pm Pm1 Pm2 Pm3 W Potenza rea...

Страница 3: ...hase input voltage range 0 1 2Vn nominal input current 5A input current range 0 1 2 In continuous overload 1 5Vn 2In instantaneous overload 1 sec 2Vn 20In programmable external TV ratio 1 99999 programmable external TV ratio 1 99999 averaging time interval AC period 1 sec accuracy voltage current active power 0 2 of reading 5 100 of input range 45 65 Hz temperature coefficient 0 01 C RS485 serial ...

Страница 4: ...ia di rete Ethernet a 10 Mbit s in reti miste 10 100 1000 Mbit s ciò non costituisce un problema purché l E1200 venga collegato a uno switch di rete Evitare invece di usare uno hub in quanto ciò rallenterebbe anche i dispositivi in grado di comunicare fra di loro a velocità maggiore Lo strumento è dotato di un connettore di rete standard RJ45 e ha la seguente configurazione di default Indirizzo IP...

Страница 5: ...legare l E1200 a uno switch di rete con un cavo normale se l E1200 è stato correttamente configurato a questo punto sarà accessibile con un browser da qualsiasi PC collegato alla rete Lo strumento è completamente configurabile per mezzo del web server Il web server consente inoltre la visualizzazione di tutti i valori misurati e calcolati The E1200 network analyzer does not support DHCP and theref...

Страница 6: ...put modules V mA Outputs For each E3000 analog output max 4 E3000 modules 12 analog outputs Output type 0 10V 4 20mA Normal inverted output e g 4 20 or 20 4 mA Output function for power factor readings Low range of output variable High range of output variable Reset readings Individual commands allow to reset Max average power values Min max values of all the readings Energy values SERVER MODBUS T...

Страница 7: ...pronti a ricevere quando l E1200 inizia a rispondere SWFP ordine di trasmissione delle due word dei valori floating point valori validi 0 1 vedi protocollo Modbus nota 2 Parametro configurabile solo per la seconda porta seriale PROT selezione Modbus slave PROT 2 default oppure Modbus master PROT 4 per pilotaggio moduli di output analogico E3000 Impostazioni default di fabbrica per entrambe le port...

Страница 8: ...23 bits SWFP Command Setting to 0 word A will be sent before word B setting 1 word B will be sent before word A Modbus RTU implemented exception codes 1 illegal function invalid or non implemented function 2 illegal data address read or write request at an invalid address Ex Non existent register read one word only of a floating point value 3 illegal data value write request of an invalid value e ...

Страница 9: ... picco I3 nell ultimo periodo AC I3 peak value in last AC period A 158 159 Float Read only S3 Potenza Apparente fase 2 Apparent power Phase 2 VA 160 161 Float Read only PF3 Fattore di potenza fase 3 Power factor Phase 3 162 163 Float Read only THD V3 Distorsione armonica totale V3 Total harmonic distortion V3 164 165 Float Read only THD I3 Distorsione armonica totale I3 Total harmonic distortion I...

Страница 10: ...Phase 2 Average Neg Act Power W 284 285 Float Read only QMMP2 Max Potenza reatt pos media fase 2 Max Phase 2 Average Pos React Power VAR 286 287 Float Read only QMMN2 Max Potenza reatt neg media fase 2 Max Phase 2 Average Neg React Power VAR 288 289 Float Read only PMMP3 Max Potenza att pos media fase 3 Max Phase 3 Average Pos Act Power W 290 291 Float Read only PMMN3 Max Potenza att neg media fas...

Страница 11: ... potenza del sistema trifase The three phase power factor 2280 2281 2480 2481 Float Read only Corrente di neutro Neutral current A Tab 3 REGISTRI DEI PARAMETRI PARAMETER REGISTERS Register Type Read Write Label Description Value Unit 300 301 Float Read only TAP Ingresso nominale I Rated I Input A 302 303 Float Read only TVP Ingresso nominale V Rated V Input V 304 305 Float Read Write ETAR Rapporto...

Страница 12: ...ll uscita function applied to output Tab 8 2708 Int Read Write AOS13 E3000 mod 1 out 3 selezione misura in uscita output reading selection 6 100 180 2709 Int Read Write AOT13 E3000 mod 1 out 3 tipo di uscita output type Tab 7 2710 Int Read Write AOI13 E3000 mod 1 out 3 uscita normale invertita normal inverted output 0 1 2711 Int Read Write AOF13 E3000 mod 1 out 3 funzione applicata all uscita func...

Страница 13: ... 2 out 2 fine campo misura output high range 7 2820 2821 float Read Write AOL23 E3000 mod 2 out 3 inizio campo uscita output low range 7 2822 2823 float Read Write AOH23 E3000 mod 2 out 3 fine campo misura output high range 7 2824 2825 float Read Write AOL31 E3000 mod 3 out 1 inizio campo uscita output low range 7 2826 2827 float Read Write AOH31 E3000 mod 3 out 1 fine campo misura output high ran...

Страница 14: ... which word has to be sent first so set this parameter to have them sent in the order that your master Modbus equipment understands MSB LSB seeeeeee emmmmmmm mmmmmmmm mmmmmmmm word A word B s segno del numero 1 se il valore è negativo 0 se il valore è positivo Sign bit negative it is 1 positive it is 0 e esponente a 8 bit 8 bit exponent m mantissa del numero 23 bit The mantissa which is code in 23...

Страница 15: ... campo verificare che la rete RS485 sia cablata a regola d arte soprattutto per collegamenti di lunghezza elevata e con molti slave connessi usare doppino schermato di buona qualità collegare la calza al terminale 0 degli slave mettere la calza a terra in un unico punto evitare diramazioni della linea e collegamenti a stella montare la resistenza di terminazione 120 ohm ai due estremi della linea ...

Страница 16: ...ve cable too long or wrong type defective network switch 2 Check if the web server works otherwise verify the E1200 network configuration IP address netmask as detailed in the Ethernet interface section of this manual The E1200 IP address must be different from any already assigned static IP address and out of the range of dynamic IP addresses managed by DHCP 3 Check if the E1200 and your Modbus T...