4 INSTALLATION
0440 001 001
- 11 -
© ESAB AB 2020
Rating plate with supply connection data
Recommended fuse sizes and minimum cable area
Mig C200i
Mains voltage
Mains cable area mm
2
Phase current,
l
eff
Fuse anti-surge
230 V ±15% 1~ 50/60 Hz
3G 1.5 mm
2
10 A
16 A
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with
Swedish regulations. For other regions, supply cables must be suitable for the
application and meet local and national regulations.
Extension cable
If needed, it is recommended to use an extension cable, 3G 2.5 mm
2
, of a maximum length
of 50 m.
Supply from power generators
The power source can be supplied from different types of generators. However, some
generators may not provide sufficient power for welding. The generators with AVR,
equivalent or better type of regulation with rated power 5.5 - 6.5 kW are recommended to
supply the power source within its full capacity.
It is also possible to use generators with lower rated power, starting from 3.0 kW, but in that
case the setting must be proportionally limited. The power source is protected against
undervoltage. If the power supplied by the generator is not sufficient, the welding is
interrupted. Especially the welding start could be disturbed. In case of disturbed welding
process, either adjust the welding parameters or change to a more powerful generator.