Adjusting the heater
1
Mount the flue gas outlet in accordance with the
local regulations.
2
Make sure the outside air supply
5
between the
operating box and the chimney is connected.
CO
2
O
2
CO
5
▷
The heater is set to the gas type specified in the
purchase order.
3
Check whether the values in the table for gas
type and adjusting range correspond to local
conditions.
Heating value H
s
[MJ/m
3
]
Minimum
Maximum
Natural gas L G 25
30.58
35.05
Natural gas H G 20
34.04
40.75
LPG G 30
90.76
125.75
▷
The fine adjustment on the gas combination
control is made on the basis of the flue gas
measurements on the chimney.
▷
The following are required for setting:
– 2.5 mm Allen key,
– Pressure gauge with display range 0 to 50 mbar,
– Flue gas analyzer. The flue gas analyzer must be
able to measure λ (lambda), O
2
, CO and CO
2
.
The sensor should be suitable for temperatures
of up to 300°C.
▷
The inlet pressure p
u
must comply with the
technical data, see page 26 (Technical data).
Important! Always check the inlet pressure when
the RGA 100 is in operation.
▷
The burner pressure p
G
can be measured using
a test point
3
between the combination control
and the housing wall.
0
3
4
Open the pressure test point for p
G
3
.
▷
Do not use force!
5
Connect a pressure gauge to
3
.
6
Disconnect the system from the electrical power
supply.
▷
The heater may only be disconnected from the
electrical power supply once the device has been
switched off and post-cooling is complete.
7
Shut off the gas supply.
CO
2
O
2
CO
100 mm
6
8
Drill a hole in the flue gas pipe 100 mm above
the stainless steel housing of the RGA 100 to
insert the flue gas analyzer sensor.
9
Insert the sensor into the hole
6
and position
in the centre of the flue gas pipe.
10
Ensure that there is no air in the gas system.
11
Switch on the power supply.
12
Release the gas supply.
13
Measure the CO, λ and O
2
values simultaneously
and observe them.
14
Switch on the burner control unit. Press ON/OFF
OFF
1
2
3
4
5
AUTO
+AUT
MODE
(RESET)
ON/OFF
O
until an LED lights up.
▷
The burner control unit switches on in the last
operating mode selected.
15
Select operating mode
2
Heating.