iPlex Installation and Hardware Specification Guide
31
DC Power and
Grounding
Requirements
The chassis has only one power terminal with no redundant connection points for
two CO power sources.
ATTENTION!
It is important to maintain proper air circulation through the iPlex
chassis. Failure to maintain proper air flow and adequate air space
can cause the iPlex to overheat and fail. Since the iPlex airflow is
from side-to-side it is recommended that you maintain a minimum 6-
inch (15 cm) clearance on both sides between the chassis air intake
and air exhaust on the sides and a cabinet wall or other barrier. You
should also calculate the heat load from other heat generating
devices and determine if an off-set is required between units to mini-
mize the effects of heat exhaust. Always allow a minimum separation
between the hot air exhaust on one chassis and the air intake on
another chassis.
STATUS
ACTIVE
LINK AC
TIVE
ALARM
POWE
R
ONLINE
SCM
MCM
ETH1
ETH2
GE 1
GE 2
MAJOR
MINOR
WARNING:
DANGER!
Install a protective earth (PE) or ground connection before
connecting power supply and telecommunication lines, using wire
gauge in accordance with this document and local codes.
Use a power source that provides current overload protection and is
rated as indicated in this document.
Содержание TANDBERG Television iPlex N20001
Страница 8: ...8...
Страница 12: ...iPlex Installation and Hardware Specifications Guide 12...
Страница 13: ...13 Introducing TANDBERG Television iPlex Chapter 1...
Страница 24: ...24 iPlex Installation and Hardware Specification Guide...
Страница 25: ...25 Hardware Specification and Installation Chapter 2...
Страница 72: ...72 iPlex Installation and Hardware Specification Guide...
Страница 73: ...73 Control Station Setup Chapter 3...
Страница 88: ...88 iPlex Installation and Hardware Specification Guide...
Страница 89: ...89 Connecting iPlex to the Internet Firewall Issues Appendix A...
Страница 98: ...Beta Beta iPlex Installation and Hardware Specifications Guide 98...