2. Installation
RC520 Safety and Installation Rev.2
36
30B
Pin Assignments
The EMERGENCY connector pin assignments are as follows:
Pin No.
Signal
Function
1 E_SW11
2 E_SW12
Emergency Stop switch output (1)
*3
3
E.STOP1+
Emergency Stop input 1 (+)
4
E.STOP1
-
Emergency Stop input 1 (
-
)
5 E.STOP
OUT
6 E.STOP
OUT
Emergency Stop condition output
(Relay contact)
*1
7 GUARD11
8 GUARD12
Safety Door input (1)
*2
9 +24V
+24V
output
10
+24VGND
+24V GND output
11 E_SW21
12 E_SW22
Emergency Stop switch output (2)
*3
13
E.STOP2+
Emergency Stop input 2 (+)
14
E.STOP2
-
Emergency Stop input 2 (
-
)
15 RELEASE
16 RELEASE
Latch Release input
17 GUARD21
18 GUARD22
Safety Door input (2)
*2
19 +24V
+24V
output
20
+24VGND
+24V GND output
*1 The Emergency Stop condition is output via relay contact when it is open (it is
normally closed).
*2 A critical error occurs if the input values from Safety Door 1 and Safety Door
2 are different for two or more seconds. They must be connected to the same
switch with two sets of contacts.
*3 The signal from the Emergency Stop switch is designed to use two redundant
circuits. An error occurs if the statuses of the two redundant circuits are
different for two or more seconds. They must be connected to the same
switch with two sets of contacts.