remote override. Or if the event
ends and the system is configured to
Auto Exit
26
Demand Response Notifies that a demand response
event is currently in progress. Will be
reset either by the manual override
push button, or remote override. Or
if the event ends and the system is
configured to Auto Exit
1/0
1
Interval
and Delta
-
Read Only
359
Switch
The position of the switch. Writing 1
to the switch initiates a DR Event,
while writing 0 to the switch ends a
DR Event. Note that the switch could
be ON, when no event is in progress
if the system is waiting for a manual
Exit.
1/0
1
Interval
and Delta
-
Read/Write
User Interface Sensors
These sensors provide data on the state of the user interface and can be used to trigger state changes at the
NOC or for audit/compliance purposes.
Sensor ID
Data Feed
Description
Unit
Resolution Reporting Default
Read/Writ
e
41
Key Switch
The position of the key switch. 1 =
Armed, 0 = Not Armed
-
1
Interval
and Delta
-
Read Only
42
Exit Button
The position of the Exit Button, 1 =
pressed, 0 = released
-
1
Interval
and Delta
-
Read Only
250
Enter Event Value
An Echo of the Enter Event Value
Property 6501 which allows this to
be exported as a Sensor in the
normal fashion
-
1
Snap to
Clock
-
Read Only
251
Exit Event Value
An Echo of the Exit Event Value
Property 6502 which allows this to
be exported as a Sensor in the
normal fashion
-
1
Snap to
Clock
-
Read Only
Electricity Metering Sensors
These read-only ‘sensors’ provide data on the power consumption and frequency of the 3-phase system that the
ZDR is monitoring.
Sensor ID
Data Feed
Description
Unit
Resolution Reporting Default
Read/Writ
e
300
Phase A kWh
Phase A kWh value. This is a
continually increasing kWh reading.
kWh
0.01
Off
-
Read/Write
301
Phase B kWh
Phase B kWh value. This is a
continually increasing kWh reading.
kWh
0.01
Off
-
Read/Write
Page 10
of 37